450 kW at 500-690 V — HVAC/water/wastewater duty cycle
The 6SL3220-2YH62-1CF0 is a SINAMICS G120X infrastructure converter rated 450 kW at 500-690 VAC +10/-20%, 47-63 Hz, with a 135% overload for 3 s, 110% for 60 s, and 100% for 240 s. That overload profile matches pump and fan starting torque requirements where the drive sees a brief inrush from a stopped impeller, then settles to continuous duty. Size FSH enclosure with IP20 / UL open type protection means it mounts inside a clean, dry electrical room or MCC lineup — not on the machine frame. The RFI suppression filter is category C3, so it's suited for industrial networks where the supply transformer is dedicated to the drive system, not residential or light commercial feeders.
Fieldbus and IO — PROFINET PN, Ethernet IP, expansion slot
Fieldbus is integrated: PROFINET PN and Ethernet IP on board, no separate communication module needed. That saves a slot and simplifies the device-level network configuration for a plant running Siemens S7 or Rockwell ControlLogix controllers. The IO expansion and Basic Operator Panel are included in the base unit — no add-on kit required for local parameter access or additional digital/analog I/O points. The operator panel lets a field tech commission the drive without a laptop for basic speed and ramp settings.
Active production — mature lifecycle, no phase-out signal
Export control classification is AL: N / ECCN: EAR99H, so no special license required for most commercial shipments. RoHS compliance effective since 11-03-20; REACH Article 33 declares lead (CAS 7439-92-1) above 0.1% w/w, which is typical for power semiconductor solder joints and busbar plating.