500 kW at 690 V — overload profile for fan/pump cycling
The 6SL3220-2YH64-0CF0: Rated 500 kW continuous with a 135 % overload for 3 seconds or 110 % for 60 seconds, then 100 % for 240 seconds — the duty cycle matches centrifugal load profiles where starting torque peaks briefly and running torque settles below nameplate. Input accepts 3AC 500-690 V +10/-20 % at 47-63 Hz, covering 690 V class installations common in European water infrastructure and mining without a step-down transformer. The integrated EMC filter meets Category C3, meaning conducted emissions are suppressed for industrial second-environment networks — not for residential or public low-voltage grids.
Frame FSJ — panel integration and fieldbus
Frame size FSJ is the largest in the G120X family; the enclosure is IP20 / UL Open Type, so it must be mounted inside a panel or cabinet that provides the environmental seal and touch-safe barrier. Integrated fieldbus is PROFINET-PN and EtherNet/IP — dual-protocol on the same port, so the drive drops into a Siemens or Rockwell line without a gateway module. A Basic Operator Panel ships with the unit, giving local start/stop, speed reference, and parameter navigation without a connected PC or fieldbus master.
Active production — made-to-order class C
Product class C means this unit is manufactured to order — it cannot be reused, re-utilized, or returned for credit. Confirm the BOM line before committing. RoHS compliant since 11 March 2020; REACH Article 33 disclosure notes Lead CAS-7439-92-1 above 0.1 % w/w in the candidate list.