Skip to main content
Siemens 6SL3220-3YE58-0CP0 — AC Drives (VFD)

Siemens 6SL3220-3YE58-0CP0 SINAMICS G120X, 355 kW, 380-480 V

MPN6SL3220-3YE58-0CP0
Active

Siemens SINAMICS G120X infrastructure converter, 355 kW, 3AC 380-480 V, RFI C3 filter, IP20, PROFIBUS DP, size FSH.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

6SL3220-3YE58-0CP0 — Identification
ParameterValue
Product familySINAMICS G120X infrastructure converters for HVAC/Water/Wastewater

Other specifications

6SL3220-3YE58-0CP0 — Other specifications
ParameterValue
Group codeR220
Product group4R53
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
Export control regulationsAL : N / ECCN : 9N9999
Compliance with the substance restrictions according to RoHS directiveSince: 11-03-20

Product details

355 kW drive for HVAC and water infrastructure

The 6SL3220-3YE58-0CP0 is a SINAMICS G120X infrastructure converter rated 355 kW with a 135% overload capability for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds — the overload profile matches typical pump and fan duty cycles where short-duration starting torque or transient load spikes are absorbed without oversizing the drive. It accepts 3AC 380-480 V +10/-20% at 47-63 Hz and includes a built-in RFI suppression filter for Category C3 environments, meaning it meets conducted emission limits for industrial power networks without an external filter. The drive ships with an Intelligent Operator Panel (IOP) for local parameterisation and diagnostics, and integrates PROFIBUS DP as the fieldbus interface — no IO expansion module is fitted as standard.

Sizing and overload envelope for motor matching

The 135% / 3-second overload ceiling is the key sizing constraint: a 355 kW motor with a starting current transient that exceeds this will trip the drive unless the acceleration ramp is extended or the motor is oversized relative to the load. Ambient temperature range is 0 to +45 °C; above 45 °C the continuous output current must be derated per the SINAMICS G120X manual — the IP20 / UL open-type enclosure relies on the cabinet's forced-air cooling, not its own fan, so panel airflow is the derating lever. Size FSH frame — the packaging footprint is 800 x 1870 x 600 mm, which dictates the cabinet depth and lifting provisions during installation.

Compliance and regulatory documentation

RoHS compliant since 11 March 2020; the REACH Article 33 duty-to-inform applies due to lead (CAS-No. 7439-92-1) above 0.1% w/w in certain components — this must be communicated down the supply chain per EU REACH regulation. Export Control Classification: AL=N, ECCN=9N9999 — no special licensing required for most destinations, but the buyer should verify end-use restrictions if the drive is destined for a sanctioned region. Product class C means this unit is manufactured to order and cannot be returned for credit — confirm the BOM line before committing.

Sourcing and lifecycle posture

Sourced through authorised distribution channels; quoted to order against the BOM quantity with availability and current pricing confirmed at RFQ time.

Frequently asked questions

What compliance documentation does this drive carry?

RoHS compliant since 11 March 2020. REACH Article 33 applies due to lead content above 0.1% w/w. Export Control: AL=N, ECCN=9N9999. The drive includes a built-in RFI filter for Category C3 industrial environments.

What is the overload capability and how does it affect motor selection?

The drive delivers 135% rated current for 3 seconds, 110% for 60 seconds, and 100% for 240 seconds. For a 355 kW motor, the starting transient must stay within the 135% / 3-second window, or the acceleration ramp must be extended to avoid an overcurrent trip.

MPN
6SL3220-3YE58-0CP0