The K-curve trips magnetically between 8 and 12 times rated current — designed for inductive loads like motors, transformers, and solenoid valves where inrush current would nuisance-trip a B- or C-curve breaker. On a 277 VAC line it interrupts faults up to 6 kA; on a 500 VDC circuit it handles 10 kA, covering most industrial control panels and DC distribution. The 2-pole form factor fits a single module width per pole, so it occupies two 18 mm slots in a distribution board.

ABB S202MUC-K50 MCB 2P K 50 A, DIN Rail
MPN S202MUC-K50
ABB S200MUC series, miniature circuit breaker MCB, 2-pole, Trip Curve K, 50 A, 277 VAC / 500 VDC, 6 kA AC / 10 kA DC interrupting, DIN-rail mount.
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product type | Trip Curve K |
| Voltage | 500 V |
| Current | 50 A |
| Breaking capacity | 6 kA |
| Poles | 2 |
| Mounting | DIN Rail |
Product details
S202MUC-K50 Datasheet
MPN
S202MUC-K50