Skip to main content
Siemens 3RT2015-2AH01-ZX95

Siemens 3RT2015-2AH01-ZX95 SIRIUS Contactor, Size S00, 45 mm

MPN 3RT2015-2AH01-ZX95
Active

Siemens SIRIUS 3RT2015-2AH01-ZX95 power contactor, Size S00, 45 mm width, spring-type coil terminals, screw and snap-on mounting on 35 mm DIN rail (DIN EN 60715), 73 mm depth.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RT2015-2AH01-ZX95 specifications
ParameterValue
Depth73 mm
Width45 mm
Height70 mm
Arcing time10 ... 15 ms

Product details

Lifecycle and Sourcing Reality

The 3RT2015-2AH01-ZX95: As a current-production Siemens SIRIUS contactor, it is sourced through authorized distribution channels. Availability and current pricing are confirmed at RFQ against the BOM quantity.

Panel Fit and Mounting

Size S00 frame: 45 mm wide, 70 mm tall, 73 mm deep. The width is the critical dimension for DIN-rail density — at 45 mm it occupies one standard 45 mm module position on a 35 mm rail per DIN EN 60715. Mounting is dual-mode: screw-fixed or snap-on onto 35 mm standard mounting rail. The mounting position allows +/-180° rotation on a vertical surface and +/-22.5° tilt forward/backward, giving flexibility in tight enclosures. Clearance requirements: 10 mm upward, 10 mm forward, 10 mm downward, 6 mm at the side. These are the minimum air gaps for heat dissipation and arc flash clearance.

Wiring and Terminals

Main contact terminals accept solid or stranded wire: 0.5 to 4 mm² per conductor, or 2x (0.5 to 4 mm²) for paralleled feeds. The coil terminals are spring-type — push-in termination, no screw torque required. The auxiliary switch is factory-fitted (yes), so no separate add-on block is needed for basic signaling or interlocking.

Switching Performance and Duty Cycles

Rated for AC-1 (resistive) duty up to 1,000 operations per hour, AC-2 and AC-3 (motor starting) at 750 ops/h, and AC-4 (plugging/inching) at 250 ops/h. The AC-3e rating matches the AC-3 figure at 750 ops/h. Opening time (at AC) is 7 to 13 ms; arcing time is 10 to 15 ms. These timing windows are relevant for coordination with upstream protective devices and for assessing contact wear in high-cycle applications. Mechanical life of the contactor is typical 30,000,000 operations — a high-cycle rating suited for frequent switching in conveyor or pump control.

Environmental and Storage

Operating temperature range: -25 to +60 °C. Storage range: -55 to +80 °C. This covers most industrial enclosures and unheated warehouses.

MPN
3RT2015-2AH01-ZX95