Skip to main content
Siemens 3RW5215-1TC15

Siemens 3RW5215-1TC15 Soft Starter, 200-600 V, 11.5 A

MPN 3RW5215-1TC15
Active

Siemens 3RW5215-1TC15 soft starter, 200-600 V rated, 11.5 A minimum, CLASS 10A/10E/20E per IEC 60947-4-2, PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET, screw fixing.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5215-1TC15 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1

Product details

Soft starter for motor starting duty

The Siemens 3RW5215-1TC15 is a hybrid switching device — a soft starter — rated for motor control across 200 to 600 V AC (50/60 Hz). Its minimum settable current is 11.5 A, and it offers three trip classes per IEC 60947-4-2: CLASS 10A (default), CLASS 10E, and CLASS 20E. This means the overload protection curve can be matched to the motor's starting profile — CLASS 10A for standard starts, CLASS 20E for high-inertia loads like fans or centrifuges where the start time extends beyond 10 seconds. The unit supports multiple industrial fieldbus protocols natively: PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard. It also includes PROFIenergy capability when paired with the PROFINET communication module, allowing energy-saving idle states during production pauses.

Trip class and thermal management

Trip class selection is critical for motor protection coordination. CLASS 20E extends that window to 20 seconds — necessary for loads with high starting inertia where the motor takes longer to reach full speed. If the trip class is set too fast for the application, nuisance tripping during start-up will occur; too slow and the motor winding may overheat before the starter disconnects. In a panel with poor airflow or adjacent heat sources, the effective current rating drops — plan the thermal budget accordingly. The unit is screw-fixed to the mounting surface, not DIN-rail snap-on, so panel layout must account for the 170 mm width and 275 mm height with clearance: 100 mm upward, 10 mm forward, 75 mm downward, and 5 mm at the sides.

MPN