Siemens 3RW5216-1TC15

Siemens 3RW5216-1TC15 Soft Starter, 200-600 V, 14 A Min

MPN 3RW5216-1TC15
Active

Siemens 3RW5216-1TC15 soft starter, 200…600 V, 14 A minimum, Trip Class 10A/10E/20E, PROFIBUS/Modbus/EtherNet/IP/PROFINET, 170 x 152 x 275 mm.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5216-1TC15 specifications
ParameterValue
Mountingscrew fixing
Depth152 mm
Width170 mm
Height275 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1

Product details

Trip class and motor protection curve

The 3RW5216-1TC15 is set up for Trip Class 10A by default, with selectable 10E and 20E per IEC 60947-4-2. Class 10A clears an overload in under 10 seconds at 7.2× FLC — tight enough to protect standard squirrel-cage motors during starting without nuisance tripping on high-inertia loads. Class 20E buys you extra time for loads like crushers or centrifugals that need a longer ramp. Minimum adjustable current is 14 A, which sets the floor for the motor FLC you can protect. Below that rating, the overload curve won't calibrate correctly.

Fieldbus and control integration

This soft starter carries onboard PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET — no separate communication module needed for most networks. The PROFINET interface also supports PROFIenergy for coordinated energy management during idle phases. Remote reset is handled by cycling the control supply voltage — useful for unattended restart after a fault clears.

Pump and torque control features

Pump Ramp Down is included — it extends the deceleration time to reduce water hammer in pump applications. Soft Torque mode provides a gentler acceleration profile for high-inertia loads like conveyors or centrifuges. Torque Control is not available on this unit — if you need closed-loop torque regulation during start, step up to the higher-feature variant.

Thermal derating and panel layout

In a sealed panel with other heat sources, budget for reduced continuous current above that threshold. Mounting is screw-fix to a vertical surface, rotatable ±90° and tiltable ±22.5° front-to-back. Clearance requirements: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the sides, 0 mm backwards — tight enough for most enclosures. Dimensions are 170 mm wide, 152 mm deep, 275 mm high — fits a standard 600 mm deep cabinet with room for wiring ducts.

Wiring and termination

That covers both control wiring and main power cables up to about 8 AWG.

Approvals and compliance

Carries UL, CSA, and CE marking — accepted for panel builds in North America and the European Union without additional certification work.

MPN
3RW5216-1TC15