Skip to main content
Siemens 3RW5225-3TC04

Siemens 3RW5225-3TC04 SIRIUS Soft Starter, 200-480 V

MPN 3RW5225-3TC04
Active

Siemens SIRIUS 3RW5225-3TC04 hybrid soft starter, 200-480 V AC, 25.5 A minimum current, Trip Class 10A/10E/20E, screw fixing, 306x185x203 mm, CE/UL/CSA.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5225-3TC04 specifications
ParameterValue
Mountingscrew fixing
Depth203 mm
Width185 mm
Height306 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1
Digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)

Product details

Motor voltage and overload protection profile

Rated for 200-480 V AC supply, the 3RW5225-3TC04 covers the common low-voltage motor range across 230 V, 400 V, and 480 V systems — a single part number spans both European and North American line voltages. The minimum operating current of 25.5 A sets the lower bound of the motor FLA it can protect; below this threshold the overload curve cannot be set accurately, so the motor must draw at least 25.5 A at full load. Trip class is configurable as CLASS 10A (default), 10E, or 20E per IEC 60947-4-2 — this determines how long the soft starter allows locked-rotor current before tripping, with 10A being the fastest (10 seconds at 7.2× Ie) and 20E the slowest, matching the thermal capacity of the motor winding.

Fieldbus and control integration

Supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET — the soft starter can be dropped into virtually any industrial network topology without a separate gateway. PROFIenergy capability is available when paired with the PROFINET communication module, allowing the drive to participate in coordinated energy-saving shutdowns during production pauses. Remote reset is achieved by cycling the 24 V DC control supply voltage — no physical pushbutton access needed at the panel door.

Clearance and mounting envelope

Dimensions 306 mm height, 185 mm width, 203 mm depth — the unit occupies a standard-size panel footprint and mounts via screw fixing to a vertical surface. Required clearances: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, 0 mm behind — these ensure adequate airflow for the -25 to +60 °C operating range (derating applies above 40 °C). Mounting position allows ±10° rotation and tilt forward or backward on a vertical surface, giving some flexibility in tight enclosures.

Application-specific starting profiles

Soft Torque and Pump Ramp Down are built-in features — Soft Torque reduces mechanical shock on geared loads, while Pump Ramp Down eliminates water hammer by extending the deceleration ramp on pump motors. Auto-reset is supported, meaning the starter can restart automatically after a fault clears, reducing downtime in remote or unmanned installations.

Regulatory approvals and compliance documentation

CE marking covers the European Low Voltage and EMC Directives; UL and CSA approvals cover the North American market — the part carries the marks needed for panel certification in both regions. The pollution degree is 3 per IEC 60947-4-2, meaning the unit is designed for conductive pollution environments (condensation, light dust) typical of industrial control panels without sealed enclosures.

MPN