Skip to main content
Siemens 3RW5248-6TC05

Siemens 3RW5248-6TC05 SIRIUS Soft Starter, 240 A, 200–600 V

MPN 3RW5248-6TC05
Active

Siemens SIRIUS 3RW5248-6TC05 hybrid soft starter, 240 A minimum, 200–600 V, trip class 10A/10E/20E, screw fixing, PROFIBUS/Modbus/EtherNet/IP/PROFINET, CE/UL/CSA.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

3RW5248-6TC05 specifications
ParameterValue
Mountingscrew fixing
Depth203 mm
Width210 mm
Height393 mm
Trip classCLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2
Service factor1

Product details

Motor load range and trip class

The 3RW5248-6TC05 is a SIRIUS hybrid soft starter rated for a minimum motor current of 240 A across a line voltage range of 200–600 V. That 240 A floor means it is sized for medium-horsepower motors — think 150–200 HP at 480 V — where the starting current inrush would otherwise slam the contactor and trip upstream breakers. Trip class is configurable between CLASS 10A (default), 10E, and 20E per IEC 60947-4-2.

Fieldbus and control integration

Built-in fieldbus support covers PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard — so it drops into most common control networks without an external gateway. PROFIenergy is available when paired with the PROFINET communication module, letting the drive participate in energy-management profiles during idle phases. Control supply is 24 V DC. Remote reset is supported by cycling the control supply voltage. The unit also supports firmware updates and an error logbook with special accessories — useful for commissioning diagnostics without a laptop.

Mounting, clearance, and environmental limits

Dimensions are 393 mm high × 210 mm wide × 203 mm deep. Clearance requirements: 100 mm above, 10 mm in front, 0 mm behind, 75 mm below, and 5 mm at the sides — plan the panel layout accordingly. Shock resistance is 15 g / 11 ms, down to 12 g / 11 ms if contact lifting is a concern. Pollution degree 3 per IEC 60947-4-2 — suitable for industrial environments with conductive dust or occasional condensation.

CE marking, UL approval, and CSA approval are all listed — covering the major North American and European regulatory jurisdictions. The service factor is 1, meaning no continuous overload margin beyond nameplate; factor this into the motor selection if the application expects occasional overloads.

MPN
3RW5248-6TC05