Siemens 5SU1354-6KK40 SENTRON RCBO, 40 A, 10 kA, Type B

MPN 5SU1354-6KK40
Active

Siemens SENTRON 5SU1354-6KK40 RCBO, 1P+N, 40 A at 30 °C, Type B tripping characteristic, 10 kA per EN 60898, 15 kA per IEC 60947-2, 50 Hz, IP20, 2 MW units.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SU1354-6KK40 specifications
ParameterValue
Poles2
Depth77 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

It carries a Type B tripping characteristic, so it trips on short-circuit currents between 3 and 5 times the rated current — standard for general-purpose residential and commercial final circuits where no special inrush or high-harmonic loads are present. Rated 40 A at 30 °C ambient, the part is designed for 50 Hz supply systems at 230/240 V AC.

Two breaking capacity ratings are listed: 10 kA according to EN 60898 (the standard for MCBs and RCBOs in household and similar installations) and 15 kA according to IEC 60947-2 (the standard for low-voltage switchgear and controlgear). Both ratings are at 230/240 V AC.

Temperature derating — the real current rating

The 40 A rating holds only at 30 °C ambient. Above that, the continuous current must be derated: 37.6 A at 40 °C, 36.4 A at 45 °C, 34.8 A at 50 °C, 32.4 A at 55 °C and 60 °C, 30.8 A at 65 °C, and 29.2 A at 70 °C.

This RCBO occupies 2 modular width units (MW) on a DIN rail — 36 mm wide, 90 mm high, 77 mm deep, with an installation depth of 70 mm. Supply can enter from either the top or bottom, which simplifies wiring in tight enclosures.

Construction and compliance

Pollution degree 2 (non-conductive pollution only) and overvoltage category III (fixed installation with downstream sub-distribution) are the rated environmental conditions. Surge voltage resistance is 4 000 V, insulation voltage (Ui) is 264 V.

MPN