Skip to main content
Siemens 5SY4206-6CC

5SY4206-6CC SENTRON MCB, B-Curve 6A 2-Pole 10kA

MPN 5SY4206-6CC

Siemens SENTRON, miniature circuit breaker, 5SY4206-6CC, 2-pole, B-curve, 6 A rated, 10 kA breaking capacity per IEC 60898, 5 kA per UL 1077.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY4206-6CC specifications
ParameterValue
Poles2
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width36 mm
Height90 mm
Energy limitation class3

Product details

Under UL 1077 and CSA C22.2 No. 235 it carries a 5 kA interrupting rating, so for a panel built to North American code the available fault current at the breaker must not exceed 5 kA.

Thermal derating — the number that matters for real loads

The 6 A rating holds at 35 °C. Above that the breaker derates: 5.51 A at 40 °C, 5.25 A at 45 °C, 4.97 A at 50 °C, 4.69 A at 55 °C. If the panel ambient runs 50 °C, size the circuit for 5 A continuous, not 6 A.

MPN
5SY4206-6CC