Skip to main content
Siemens 5SY8404-8

Siemens SENTRON 5SY8404-8 MCB, D Curve, 4 A, 4-Pole, 50 kA

MPN 5SY8404-8
Active

Siemens SENTRON miniature circuit breaker, 5SY8404-8, D characteristic, 4-pole, 4 A (45 °C), 400 V AC, 50 kA IEC 60947-2, 4 MW wide, quick-assembly system.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SY8404-8 specifications
ParameterValue
Poles4
IP ratingIP20
MountingQuick assembly system
Temp operating max75 °C
Temp operating min55 °C
Depth76 mm
Width72 mm
Height90 mm

Product details

The Siemens SENTRON 5SY8404-8 is a 4-pole miniature circuit breaker with a D tripping characteristic, rated 4 A at 45 °C ambient on a 400 V AC system. On DC circuits it's rated 15 kA per IEC 60947-2, and under UL 1077 / CSA C22.2 No. 235 it carries 5 kA at AC — relevant if the panel ships to North America under those standards. The 4-pole version (4P) switches all three phases plus the neutral — common in three-phase distribution where the neutral needs overcurrent protection or is switched for isolation. Mounting position is any; the quick-assembly system clips onto the standard DIN rail, occupying 4 modular width units (about 72 mm).

Temperature derating and environmental limits

The 5SY8404-8 is rated 4 A at 45 °C, but the current must be derated as ambient rises: 3.9 A at 50 °C, 3.8 A at 55 °C. Above that, the surrounding temperature influence curve caps at 95% relative humidity up to 55 °C, then 55% RH up to 70 °C, and 35% RH up to 75 °C maximum. The minimum storage/operating temperature is -40 °C, covering cold-start conditions in outdoor or unheated installations.

Mechanical and vibration withstand

Tested to IEC 60068-2-6 for vibration resistance: ±1 mm displacement at 5 to 25 Hz, and 50 m/s² acceleration at 25 to 150 Hz. That covers most industrial panel vibration environments — motor starters, conveyor lines, compressor skids — without the breaker nuisance-tripping or loosening on the DIN rail. Overvoltage category III and degree of pollution 3 confirm it's rated for fixed installations inside the distribution board, not for the final outlet.

MPN
5SY8404-8