What the extended temperature range means for your panel
The 6AG1052-1FB08-7BA1: The 70 °C ceiling covers the hot end of a sealed cabinet near a steam line or a roof-mounted panel in direct sun, though the display legibility and response time degrade above 55 °C and recover when the temperature drops back.
Environmental resilience beyond the standard LOGO!
Compared to the base 6ED1052-1FB08-0BA1, this SIPLUS unit adds conformal coating and resistance to diesel and oil droplets in the air, plus protection against aggressive gases up to EN 60721-3-3 class 3C4 and salt spray level LC3.
I/O complement and power supply constraints
Eight digital inputs, 115 V / 230 V AC or DC supply, and four relay outputs rated 10 A resistive or 3 A inductive. The relay contacts are good for direct switching of small contactors or solenoid valves up to 3 A inductive — beyond that, interpose a contactor. Note the absence of short-circuit protection on the outputs: external fusing is mandatory per the spec, so budget a 4 A gG fuse per output group on the BOM.
The 4 SU footprint matches the standard LOGO! form factor, so it drops into an existing drilled-and-wired panel without re-spacing the terminal blocks. The display is present and readable, though as noted the response time lengthens above 55 °C.
Program capacity and software compatibility
400 function blocks maximum, with program capacity varying by block type. The unit runs LOGO! Soft Comfort V8.3 or higher, and older projects created in earlier versions are executable after a conversion step. The integrated web server, data logging, and user-defined web pages are available over the Ethernet port. A standard microSD card handles program storage and firmware updates.