Skip to main content
Siemens 6EP3321-6SB10-0AY0

Siemens 6EP3321-6SB10-0AY0 DIN Rail PSU, 24V/2.5A

MPN 6EP3321-6SB10-0AY0
Active

Siemens 6EP3321-6SB10-0AY0 SITOP DIN-rail switched-mode power supply, 24 V / 2.5 A output, 85-264 V AC and 110-300 V DC input, 1-phase, snap-on DIN rail EN 60715, UL 508 / cULus / cURus NEC class 2.

$54.61 – $103.81 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

6EP3321-6SB10-0AY0 specifications
ParameterValue
Fuse protection typeinternal
Voltage15 V
Power28.5 W
Frequency47 ... 63 Hz
Phases1-phase
IP ratingIP20
Depth53 mm
Width36 mm
Height90 mm
Efficiency83.4%

Product details

Current SITOP line, 2.5 A continuous at 24 V

The 6EP3321-6SB10-0AY0: At 1.9 A the device holds full output up to +55 °C with natural convection; from +55 °C to +70 °C the rating derates linearly at 2 % per kelvin, which is the figure the panel thermal budget has to respect when the cabinet sits above a heat source or in a sealed enclosure.

Wide-range input and feeder coordination

Input accepts 85 V to 264 V AC at 47 to 63 Hz, plus a DC window of 110 V to 300 V — that covers single-phase industrial mains worldwide and lets the same unit ride a DC back-up bus during a mains dropout without re-specification. The recommended upstream protection is a 6 A characteristic B or 2 A characteristic C miniature breaker, sized to ride the inrush I²t of 0.8 A²·s without nuisance tripping. Output SELV per EN 60950-1 and EN 50178 with internal fusing — the isolation barrier is what allows the 24 V rail to be run to operator-accessible terminals without additional protection.

Panel fit, clearances, and approvals

Mounting is a snap onto DIN rail EN 60715 35x7.5/15, with direct mounting supported in different orientations; the listed clearance envelope is 20 mm top, 20 mm bottom, 0 mm left and right, which is what dictates the side-by-side stacking pattern in the cabinet. The IP20 rating is finger-safe from the front but does not extend to the screw terminals, so a terminal cover is needed if the cabinet door opens into an operator zone. Approvals cover cULus-Listed under UL 508 and CSA C22.2 No. 107.1 (File E197259), cURus-Recognized under UL 60950 and CSA C22.2 No. 60950 (File E151273) with NEC class 2 per UL 1310, plus EAC and DNV GL marine — the marine register is what allows the same part number into a bridge or engine-room cabinet without a separate spec. ATEX and IECEx are not on the certificate, so hazardous-area cabinets still need an Ex-rated supply upstream.

Reliability and procurement posture

MTBF at 40 °C is 2,938,542 h — a figure that supports long-spare stocking for an MRO shelf without a refresh cycle.

MPN
6EP3321-6SB10-0AY0