The 3ABD00037857-D: Normal-use output (156 A) covers constant-torque applications like pumps and fans at 90 kW. Heavy-duty (124 A, 75 kW) is the figure for high-starting-torque or cyclic loads — conveyors, crushers, extruders. Light-overload rating (148 A) sits between them. Match your motor's full-load amps to the appropriate column; the drive's thermal model handles the rest.
Installation notes
Wall-mount only — no floor-standing kit included. IP21 and NEMA 1 suit clean indoor environments. Frame R7 determines the mounting footprint and cable entry layout; verify panel depth against the drive's heat sink projection. Efficiency class IE2.