Skip to main content
ABB 3ABD00038182-D — AC Drives (VFD)

ABB 3ABD00038182-D ACS880-01 VFD, 18.5 kW, 34 A, IP21

MPN3ABD00038182-D
Active

ABB ACS880-01 wall-mounted single drive, 18.5 kW / 34 A normal use, 380-500 V three-phase, IP21, frame R3.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00038182-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00038182-D — Power & Current
ParameterValue
Output power, normal duty18.5 kW
Output power, heavy duty15 kW
Output power, light-overload duty18.5 kW
Output current, heavy duty27 A
Output current, normal duty34 A
Output current, light-overload duty32 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00038182-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP21
NEMA enclosure typeType1

Mechanical

3ABD00038182-D — Mechanical
ParameterValue
Frame sizeR3
Mounting typeWall-mounted

Product details

The ABB 3ABD00038182-D is an ACS880-01 wall-mounted single drive rated for 18.5 kW normal use at 34 A output, with heavy-duty capability at 15 kW / 27 A. Input voltage range is 380 to 500 V three-phase, 47.5 to 63 Hz. Enclosure is IP21, NEMA Type 1, frame size R3.

Normal-use rating (18.5 kW / 34 A) covers constant-torque loads like conveyors and pumps at full spec. Heavy-duty rating (15 kW / 27 A) applies for higher overload cycles — think crushers or extruders where peak torque exceeds 150 % for short bursts. Light-overload use matches the normal power but at 32 A, which is the current limit for variable-torque applications like fans. Pick the duty that matches your load profile; the drive's thermal model uses the selected rating for protection.

Wall-mounted, IP21, NEMA Type 1 — suitable for clean indoor environments without washdown. Frame R3 determines the mounting footprint and gland plate layout; verify clearance for top/bottom cable entry against your panel layout. The IE2 efficiency level meets current EU Ecodesign requirements for this power class.

Frequently asked questions

What is the frame size of this drive?

Frame size R3.

What is the difference between normal-use and heavy-duty ratings?

Normal use is 18.5 kW / 34 A for constant-torque loads; heavy-duty is 15 kW / 27 A for higher overload cycles. The drive's overload protection adapts to the selected duty.

MPN
3ABD00038182-D