Skip to main content
ABB 3ABD00038222-D — AC Drives (VFD)

ABB 3ABD00038222-D ACS880-01 Drive, 75 kW, 124 A, Frame R6

MPN3ABD00038222-D
Active

ABB ACS880-01, 3ABD00038222-D, LV AC industrial wall-mounted single drive, 75 kW / 124 A, frame size R6.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00038222-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00038222-D — Power & Current
ParameterValue
Output power, normal duty75 kW
Output power, heavy duty55 kW
Output power, light-overload duty75 kW
Output current, heavy duty96 A
Output current, normal duty124 A
Output current, light-overload duty118 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00038222-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP21
NEMA enclosure typeType1

Mechanical

3ABD00038222-D — Mechanical
ParameterValue
Frame sizeR6
Mounting typeWall-mounted

Product details

The ABB 3ABD00038222-D is a wall-mounted single drive rated for 75 kW normal-use output at 124 A, with a heavy-duty rating of 55 kW at 96 A. It runs on 380–500 V three-phase input, 47.5–63 Hz, and lands in frame size R6. The IP21 enclosure and NEMA Type 1 rating cover indoor installations where some dust and dripping water are present.

Three duty curves are listed: normal use (Pn 75 kW, In 124 A), heavy-duty (PhD 55 kW, IhD 96 A), and light-overload (PlD 75 kW, IlD 118 A). For a constant-torque application like a conveyor or extruder, the heavy-duty figure governs — 55 kW is the continuous rating. For variable-torque loads such as fans and pumps, the normal-use 75 kW applies. The light-overload number (118 A) sits between the two; it typically covers short-duration overload profiles.

Integration notes

Wall-mounted, frame R6. Efficiency class IE2 is standard for this generation. The WEEE category (Large Equipment, >50 cm) affects end-of-life disposal planning in EU markets.

Frequently asked questions

What is the frame size of this drive?

Frame size R6.

What input voltage and frequency does it accept?

380–500 V three-phase, 47.5–63 Hz.

What is the normal-use output rating?

75 kW at 124 A.

What is the heavy-duty output rating?

55 kW at 96 A.

MPN
3ABD00038222-D