What this drive module delivers
It is rated for 400 kW normal use at 583 A, with a heavy-duty rating of 250 kW at 414 A and a light-overload rating of 400 kW at 573 A. Input voltage range is 380-500 V, three-phase, 47.5-63 Hz. Enclosure is IP20, open type NEMA, with IE2 efficiency.
The normal-use current of 583 A is the headline number for sizing the supply and buswork. Light-overload use at 573 A suits variable-torque applications such as pumps and fans.