LV AC industrial single drive module, order code 3ABD00039353-D. 3-phase, 380 to 500 V input, 47.5 to 63 Hz. Normal-use output is 450 kW at 635 A; heavy-duty drops to 315 kW at 477 A, light-overload is 450 kW at 623 A. IE2, IP20, NEMA Open Type, Frame Size R10.
The normal-use 635 A rating is for continuous, steady loads. The light-overload rating (623 A) sits between the two; pick it when you have occasional overloads but not the full duty cycle of heavy-duty. IP20 means it's for cabinet mounting, not washdown areas. Frame Size R10 tells you the mechanical footprint and bus-bar layout — verify panel cutouts against the drive's installation manual.