Skip to main content
ABB 3ABD00039397-D — AC Drives (VFD)

ABB 3ABD00039397-D ACS880-04 Drive Module, 630 kW, 880 A

MPN3ABD00039397-D
Active

ABB ACS880-04 single drive module, 3ABD00039397-D, 380-500 V, 47.5-63 Hz, 3-phase, 630 kW / 880 A normal duty, IP20, NEMA open, frame size R11.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00039397-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00039397-D — Power & Current
ParameterValue
Output power, normal duty630 kW
Output power, heavy duty500 kW
Output power, light-overload duty560 kW
Output current, heavy duty697 A
Output current, normal duty880 A
Output current, light-overload duty857 A

Protection & Environmental

3ABD00039397-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP20
NEMA enclosure typeOpen Type

Mechanical

3ABD00039397-D — Mechanical
ParameterValue
Frame sizeR11
Mounting typeModule

Product details

The ABB 3ABD00039397-D is a low-voltage AC industrial single drive module. It's the power stage for a 3-phase motor drive, rated for 380... 500 V input at 47.5... 63 Hz. Normal-duty output is 630 kW at 880 A; heavy-duty use drops to 500 kW at 697 A, and light-overload use sits at 560 kW at 857 A. Frame size is R11, with IP20 protection and NEMA open-type enclosure.

The three duty ratings let you match the module to the load profile. Normal-duty 880 A covers continuous fan/pump duty. Heavy-duty 697 A handles high-start-torque or cyclic loads like conveyors or crushers. Light-overload 857 A is a middle ground for applications with occasional overload peaks. Pick the duty class that matches your motor's nameplate and the application's starting/peak current — don't oversize to the normal-duty number if the motor sees heavy starts.

Frequently asked questions

What is the frame size of 3ABD00039397-D?

The frame size is R11.

What is the input voltage and frequency range?

Input voltage is 380... 500 V, frequency range is 47.5... 63 Hz, three-phase.

What are the output power ratings for different duty classes?

Normal-duty: 630 kW at 880 A. Heavy-duty: 500 kW at 697 A. Light-overload: 560 kW at 857 A.