ABB 3ABD00046993-D — AC Drives (VFD)

ABB 3ABD00046993-D ACS880-01 Drive, 3 kW, 5.2 A, IP21

MPN3ABD00046993-D
Active

ABB ACS880-01 wall-mounted single drive, 3-phase, 380-500 V input, 3 kW / 5.2 A normal duty, IP21, NEMA Type 1, frame size R1.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00046993-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00046993-D — Power & Current
ParameterValue
Output power, normal duty3 kW
Output power, heavy duty2.2 kW
Output power, light-overload duty3 kW
Output current, heavy duty4.8 A
Output current, normal duty5.2 A
Output current, light-overload duty4.9 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00046993-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP21
NEMA enclosure typeType1

Mechanical

3ABD00046993-D — Mechanical
ParameterValue
Frame sizeR1
Mounting typeWall-mounted

Product details

The 3ABD00046993-D is an ABB ACS880-01 wall-mounted single drive rated for 3 kW normal-use output at 5.2 A, with heavy-duty capability at 2.2 kW / 4.8 A. It accepts 380-500 V three-phase input and covers 47.5-63 Hz line frequency. The IP21 enclosure with NEMA Type 1 rating suits indoor panel or wall mounting where drip protection is needed.

Sizing and duty

The normal-duty rating (3 kW, 5.2 A) is the continuous motor rating for most fan and pump loads. The heavy-duty curve (2.2 kW, 4.8 A) applies for constant-torque applications like conveyors or extruders where overload margin matters. Light-overload rating matches normal-duty power at 4.9 A, indicating a slight current derating under light cyclic loads.

Efficiency class

Rated IE2 efficiency. This meets the minimum for many industrial installations, though newer sites may specify IE3 or IE4. For a replacement in an existing line, IE2 is usually acceptable unless local energy codes have been updated.

Frequently asked questions

What is the frame size of this drive?

Frame size R1.

What input voltage and frequency does it accept?

380-500 V three-phase, 47.5-63 Hz.

MPN