ABB 3ABD00047005-D — Inverter / VFD

ABB 3ABD00047005-D ACS880-01 Drive, 45 kW, 77 A, IP21

MPN3ABD00047005-D
Active

ABB ACS880-01 series, wall-mounted single drive, 3ABD00047005-D, 45 kW / 77 A normal duty, 380-500 VAC 3-phase, IP21, IE2, frame R5.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00047005-D specifications
ParameterValue
MountingWall-mounted
Enclosure type NEMAType1
Input voltage380 ... 500 V
Output current, normal use77 A
Output current, Heavy-Duty use65 A
Output current, Light-Overload use73 A
Output power, normal use45 kW
Output power, Heavy-Duty use37 kW
Output power, Light-Overload use45 kW
Frequency47.5 ... 63 Hz
Phases3-phase
IP ratingIP21
Frame sizeR5
Efficiency levelIE2

Product details

Drive selection for a 45 kW motor line

The 3ABD00047005-D is the order code for an ABB ACS880-01 wall-mounted single drive rated 45 kW normal-duty output at 77 A, with a heavy-duty rating of 37 kW at 65 A. Input accepts 380-500 V three-phase, 47.5-63 Hz. Enclosure is IP21, NEMA Type 1, frame size R5. Efficiency class IE2.

Duty ratings that govern the real install

Normal-duty (light-overload) output is 45 kW / 77 A; heavy-duty output is 37 kW / 65 A. The spread matters when the motor sees constant torque below base speed or needs short-term overload headroom. A 45 kW pump on a variable-torque curve fits the normal-duty number; a 37 kW conveyor with breakaway torque needs the heavy-duty column.

Wall-mounting and enclosure

Wall-mounted enclosure rated IP21, NEMA Type 1. Suitable for indoor, non-condensing environments. Frame size R5 determines the mounting footprint and gland-plate layout; verify clearance for the IP21 top-entry cable routing before panel layout.

Frequently asked questions

What are the key ratings for this drive?

Normal-duty output is 45 kW / 77 A; heavy-duty output is 37 kW / 65 A. Input range is 380-500 V three-phase, 47.5-63 Hz. Enclosure is IP21, frame R5, IE2 efficiency.

What frame size is 3ABD00047005-D?

Frame size R5.

MPN