Skip to main content
ABB 3ABD00059524-D — AC Drives (VFD)

ABB 3ABD00059524-D ACS880-01 Drive, 7.5 kW, 14 A, R2

MPN3ABD00059524-D
Active

ABB 3ABD00059524-D, ACS880-01 series, LV AC industrial wall-mounted single drive, R2 frame, 7.5 kW normal-duty output at 14 A, 380–500 VAC 3-phase, IE2, IP21, Type 1 enclosure.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00059524-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00059524-D — Power & Current
ParameterValue
Output power, normal duty7.5 kW
Output power, heavy duty5.5 kW
Output power, light-overload duty7.5 kW
Output current, heavy duty11 A
Output current, normal duty14 A
Output current, light-overload duty13 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00059524-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP21
NEMA enclosure typeType1

Mechanical

3ABD00059524-D — Mechanical
ParameterValue
Frame sizeR2
Mounting typeWall-mounted

Product details

The ABB 3ABD00059524-D is a wall-mounted single drive for 3-phase LV AC induction motors. Its normal-duty rating is 7.5 kW at 14 A; heavy-duty mode derates to 5.5 kW at 11 A. Light-overload use stays at 7.5 kW, 13 A. Input voltage range is 380 to 500 VAC, 47.5 to 63 Hz. The R2 frame keeps the footprint compact for a 7.5 kW unit; wall-mount it with the IP21 / NEMA Type 1 enclosure.

Normal vs heavy-duty — pick the right column

The dual rating matters more than the headline kW. Normal duty (7.5 kW, 14 A) is for variable-torque loads. Heavy-duty (5.5 kW, 11 A) is the constant-torque ceiling — match that to your motor nameplate if the load profile includes starting torque or short-term overloads. Sizing against the normal-duty figure alone risks a drive that trips on a conveyor start.

Frequently asked questions

What are the normal-duty and heavy-duty ratings?

Normal duty: 7.5 kW, 14 A. Heavy-duty: 5.5 kW, 11 A. Light-overload (variable torque) is 7.5 kW, 13 A.

What is the frame size and enclosure?

R2 frame, wall-mounted, IP21 ingress protection, NEMA Type 1 enclosure.

What input voltage and frequency does it accept?

380 to 500 VAC, 3-phase, 47.5 to 63 Hz.

MPN
3ABD00059524-D