Skip to main content
ABB 3ABD00059528-D — Inverter / VFD

ABB 3ABD00059528-D ACS880-01 Drive, 22 kW, 40 A, Frame R4

MPN3ABD00059528-D
Active

ABB ACS880-01 LV AC industrial wall-mounted single drive, 3ABD00059528-D, 22 kW / 40 A normal duty, frame size R4, IP21, NEMA Type 1, IE2 efficiency.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00059528-D specifications
ParameterValue
MountingWall-mounted
Enclosure type NEMAType1
Input voltage380 ... 500 V
Output current, normal use40 A
Output current, Heavy-Duty use34 A
Output current, Light-Overload use38 A
Output power, normal use22 kW
Output power, Heavy-Duty use19 kW
Output power, Light-Overload use22 kW
Frequency47.5 ... 63 Hz
Phases3-phase
IP ratingIP21
Frame sizeR4
Efficiency levelIE2

Product details

Duty ratings and motor sizing

The 3ABD00059528-D: The normal-duty rating of 22 kW / 40 A is the primary sizing figure for most variable-torque loads such as pumps and fans. For constant-torque applications like conveyors or extruders, the heavy-duty rating of 19 kW / 34 A applies, reflecting the higher thermal stress. The light-overload rating of 22 kW / 38 A covers applications with infrequent overloads.

Frame size and mounting

Frame size R4 defines the mechanical footprint and mounting hole pattern. Wall-mounted installation is standard; the IP21 / NEMA Type 1 enclosure means the drive is not sealed against dust ingress or washdown — locate it in a cabinet or clean electrical room. Verify gland-plate clearance and cable bend radius for the incoming mains and motor leads before committing the panel layout.

Frequently asked questions

What is 3ABD00059528-D's listed frame size?

The frame size is R4, which defines the mechanical footprint and mounting dimensions for panel layout.

What are the key power ratings for 3ABD00059528-D?

Normal-duty output is 22 kW / 40 A; heavy-duty is 19 kW / 34 A; light-overload is 22 kW / 38 A. Input voltage is 380–500 V 3-phase.

MPN
3ABD00059528-D