Skip to main content
ABB 3ABD00059528-D — AC Drives (VFD)

ABB 3ABD00059528-D ACS880-01 Drive, 22 kW, 40 A, Frame R4

MPN3ABD00059528-D
Active

ABB ACS880-01 LV AC industrial wall-mounted single drive, 3ABD00059528-D, 22 kW / 40 A normal duty, frame size R4, IP21, NEMA Type 1, IE2 efficiency.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00059528-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00059528-D — Power & Current
ParameterValue
Output power, normal duty22 kW
Output power, heavy duty19 kW
Output power, light-overload duty22 kW
Output current, heavy duty34 A
Output current, normal duty40 A
Output current, light-overload duty38 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00059528-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP21
NEMA enclosure typeType1

Mechanical

3ABD00059528-D — Mechanical
ParameterValue
Frame sizeR4
Mounting typeWall-mounted

Product details

Duty ratings and motor sizing

The 3ABD00059528-D: The normal-duty rating of 22 kW / 40 A is the primary sizing figure for most variable-torque loads such as pumps and fans. For constant-torque applications like conveyors or extruders, the heavy-duty rating of 19 kW / 34 A applies, reflecting the higher thermal stress. The light-overload rating of 22 kW / 38 A covers applications with infrequent overloads.

Frame size and mounting

Frame size R4 defines the mechanical footprint and mounting hole pattern. Wall-mounted installation is standard; the IP21 / NEMA Type 1 enclosure means the drive is not sealed against dust ingress or washdown — locate it in a cabinet or clean electrical room. Verify gland-plate clearance and cable bend radius for the incoming mains and motor leads before committing the panel layout.

Frequently asked questions

What is 3ABD00059528-D's listed frame size?

The frame size is R4, which defines the mechanical footprint and mounting dimensions for panel layout.

What are the key power ratings for 3ABD00059528-D?

Normal-duty output is 22 kW / 40 A; heavy-duty is 19 kW / 34 A; light-overload is 22 kW / 38 A. Input voltage is 380–500 V 3-phase.

MPN
3ABD00059528-D