Skip to main content
ABB 3ABD00059547-D — AC Drives (VFD)

ABB 3ABD00059547-D ACS880-01 Drive, 160 kW, 260 A, IP21

MPN3ABD00059547-D
Active

ABB ACS880-01, 3ABD00059547-D, wall-mounted LV AC drive, 160 kW normal use, 260 A, 380-500 V, 3-phase, IP21, NEMA 1, IE2, frame R8.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00059547-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency47.5 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00059547-D — Power & Current
ParameterValue
Output power, normal duty160 kW
Output power, heavy duty132 kW
Output power, light-overload duty160 kW
Output current, heavy duty240 A
Output current, normal duty260 A
Output current, light-overload duty247 A
Efficiency class (IE)IE2

Protection & Environmental

3ABD00059547-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP21
NEMA enclosure typeType1

Mechanical

3ABD00059547-D — Mechanical
ParameterValue
Frame sizeR8
Mounting typeWall-mounted

Product details

The ABB 3ABD00059547-D is a wall-mounted LV AC drive rated for 160 kW normal use at 260 A, with a 380-500 V three-phase input. It carries a NEMA Type 1 enclosure and IP21 protection.

The drive lists three duty points: normal use at 160 kW / 260 A, heavy-duty at 132 kW / 240 A, and light-overload at 160 kW / 247 A. For a constant-torque load like a conveyor or positive-displacement pump, the heavy-duty figure governs — you get 132 kW continuous. For variable-torque (centrifugal fans, pumps), the normal-use 160 kW applies. The light-overload column is a short-time rating, not continuous; use it for starting or intermittent peak loads.

Wall-mounted in a NEMA 1 / IP21 enclosure — no conduit knockouts for top entry, so plan for bottom cable glanding. Frame size R8; that's a larger footprint, so verify your backplate layout before cutting the gland plate. The drive is 3-phase input only, no single-phase option.

Frequently asked questions

What is the frame size of this drive?

Frame size R8.

What is the input voltage and frequency range?

380-500 V three-phase, 47.5-63 Hz.

What is the normal-use output rating?

160 kW at 260 A.

MPN
3ABD00059547-D