Skip to main content
ABB 3ABD00059700-D — Inverter / VFD

ABB 3ABD00059700-D ACS880-04 Drive Module, 355 kW, 503 A

MPN3ABD00059700-D
Active

ABB ACS880-04 industrial drive module, 3ABD00059700-D, 355 kW normal use, 503 A, 380-500 V, 3-phase, IP20, frame R10.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00059700-D specifications
ParameterValue
MountingModule
Enclosure type NEMAOpen Type
Input voltage380 ... 500 V
Output current, normal use503 A
Output current, Heavy-Duty use361 A
Output current, Light-Overload use483 A
Output power, normal use355 kW
Output power, Heavy-Duty use250 kW
Output power, Light-Overload use315 kW
Frequency48 ... 63 Hz
Phases3-phase
IP ratingIP20
Frame sizeR10

Product details

Drive module for high-power motor control

The ABB 3ABD00059700-D is a low-voltage AC industrial single drive module with integrated position control, rated for 355 kW normal use at 503 A on a 380–500 V three-phase supply. Frame size R10, IP20 open-type enclosure.

Duty ratings that define the real load envelope

Three duty curves are on record: normal use (Pn 355 kW, In 503 A), light-overload (PlD 315 kW, IlD 483 A), and heavy-duty (PhD 250 kW, IhD 361 A). The heavy-duty figure governs continuous high-torque applications like conveyors or extruders; the normal-use rating applies where the drive sees a standard industrial duty cycle.

Module mounting — frame R10 is a cabinet-installed power section, not a standalone drive. IP20 rated, so it requires an enclosure for anything beyond a clean, dry electrical room. The open-type NEMA designation confirms no integral conduit box; incoming and outgoing cables terminate directly on the busbars or terminal block inside the panel. Position control is onboard, so no separate encoder interface card is needed for closed-loop applications.

Frequently asked questions

What is the frame size of this drive module?

Frame size R10. This is a cabinet-mount power section, not a wall-mount unit, and requires an enclosure for IP20-rated installation.

What are the key output ratings for normal, light-overload, and heavy-duty use?

Normal use: 355 kW, 503 A. Light-overload: 315 kW, 483 A. Heavy-duty: 250 kW, 361 A. The heavy-duty rating governs continuous high-torque loads; normal use applies for standard duty cycles.

MPN