Skip to main content
ABB 3ABD00059709-D — AC Drives (VFD)

ABB 3ABD00059709-D ACS880 Drive Module, 450 kW, 635 A

MPN3ABD00059709-D
Active

ABB ACS880-04 series, 3ABD00059709-D, LV AC industrial single drive module, 380-500 V, 48-63 Hz, 450 kW / 635 A normal use, IP20, R10 frame.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Electrical

3ABD00059709-D — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency48 ... 63 Hz
Number of phases3-phase

Power & Current

3ABD00059709-D — Power & Current
ParameterValue
Output power, normal duty450 kW
Output power, heavy duty315 kW
Output power, light-overload duty450 kW
Output current, heavy duty477 A
Output current, normal duty635 A
Output current, light-overload duty623 A

Protection & Environmental

3ABD00059709-D — Protection & Environmental
ParameterValue
Degree of protection (IP)IP20
NEMA enclosure typeOpen Type

Mechanical

3ABD00059709-D — Mechanical
ParameterValue
Frame sizeR10
Mounting typeModule

Product details

The ABB 3ABD00059709-D is an LV AC industrial single drive module with position control, built for a 3-phase supply at 380...500 V, 48...63 Hz. It delivers 450 kW normal-use output power at 635 A, with heavy-duty capability at 315 kW / 477 A and light-overload at 450 kW / 623 A.

The key number for motor sizing is the heavy-duty current: 477 A at 315 kW. That's the rating that governs when the drive sees a constant-torque load or frequent starts. The normal-use rating (635 A, 450 kW) applies to variable-torque loads where the motor rarely pulls full current continuously. If your application is a conveyor or a hoist, size against the 477 A heavy-duty figure — not the headline 635 A. The R10 frame is a physical size indicator; expect a module that bolts into a cabinet with the corresponding footprint and bus-bar arrangement.

Frequently asked questions

What is the frame size of this drive module?

The frame size is R10, which defines the physical mounting dimensions and bus-bar layout for the ACS880-04 series.

What are the key current and power ratings?

Normal use: 450 kW, 635 A. Heavy-duty use: 315 kW, 477 A. Light-overload use: 450 kW, 623 A. The heavy-duty current is the one to size against for constant-torque loads.

What input voltage and frequency does it accept?

Three-phase 380...500 V AC, 48...63 Hz.

What is the enclosure protection rating?

IP20, Open Type per NEMA — designed for panel-mount installation, not standalone outdoor use.

MPN