The ABB 3AXD50000047504 is an R6-frame regenerative drive rated 18.5 kW in normal use, with a 34 A output current. Heavy-duty use drops to 15.0 kW and 27 A. Light-overload use holds at 18.5 kW with 32 A output. Input voltage range is 380 to 500 V three-phase at 47.5 to 63 Hz. Power factor sits at 1.0. Enclosure is IP21 with a NEMA Type 1 rating, wall-mounted. Ambient temperature maxes at +55 °C, humidity 5 to 95%. Altitude rating is 4000 m. Standby loss runs 52 W; sound level is 71 dB(A). No end-of-life or phase-out has been announced.
Apparent power output is 29 kV·A, with power consumption at 737 W under load. The regenerative design means it can return energy to the line — the ecodesign exemption notes that energy efficiency data isn't provided because regenerative drives are exempt from EU Regulation 2019/1781. Communication is CAN-based. There are no industrial Ethernet interfaces on this variant — 0 hardware interfaces listed for that protocol. I/O includes 2 analog inputs, 2 analog outputs, 6 digital inputs/outputs, and 2 dedicated digital outputs.
WEEE category is 4 — Large Equipment with any external dimension over 50 cm. The drive includes a control unit as standard. Internal battery is a lithium coin CR2032, 220 mAh, 3 V, two pieces at 6 g total.
Wall-mounted, R6 frame. IP21 with NEMA Type 1 means it's suitable for indoor, clean environments — not for washdown or dusty locations. The 4000 m altitude rating covers most installations; above that derating applies. Operating temperature range tops out at +55 °C, humidity 5 to 95% non-condensing. Sound level at 71 dB(A) means it's audible in a quiet control room — plan for ear protection if multiple drives are in the same space.