The 3AXD50000145836: Normal-use rating at 800 kW / 1110 A is the continuous motor load for most applications — that's the line item to match against your motor nameplate. The UL ratings mirror these: 1000 Hp normal, 700 Hp heavy-duty, 900 Hp light-overload — all at the same currents, so the drive's thermal capacity is identical regardless of which standard you're quoting against.
Installation constraints
Rated for installation up to 1000 m altitude. Ambient temperature max 40 °C. Operating humidity 5–95% non-condensing. Sound level 77 dB(A).
Four analog inputs and four analog outputs are on board, plus 14 digital inputs and 10 digital outputs. Communication is CAN-based; no onboard Industrial Ethernet interface (0 hardware interfaces for that). If you need PROFINET, EtherNet/IP, or EtherCAT, an optional fieldbus adapter module is required — the drive's slot architecture supports it, but the base unit ships without it.
Compliance and regulatory notes
SCIP number 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland is registered for the part. WEEE category 4 (Large Equipment). The regenerative drive is exempt from EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c) — no energy efficiency data provided for this model. Contains two BR2032 lithium coin cells (3 V, 200 mAh each).