Skip to main content
ABB 3AXD50000145850 — Inverter / VFD

ABB 3AXD50000145850 ACS880-17 Drive, 1400 kW, 1980 A

MPN3AXD50000145850
Active

ABB ACS880-17 regenerative drive, 3AXD50000145850, 380-500 V 3-phase, 1400 kW / 1980 A normal use, IP22, Type 1, active.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000145850 key specifications
ParameterValue
Enclosure type NEMAType1
Input voltage380 ... 500 V
Output current, normal use1980 A
Output current, Heavy-Duty use1481 A
Output current, Light-Overload use1901 A
Technical UL (Output current, normal use)1980 A
Technical UL (Output current, Heavy-Duty use)1481 A
Technical UL (Output current, Light-Overload use)1901 A
Power factor1
Apparent power output1715 kV·A
Output power, normal use1400 kW
Output power, Heavy-Duty use1000 kW

All specifications

3AXD50000145850 additional specifications
ParameterValue
Output power, Light-Overload use1300 kW
Technical UL (Output power, normal use)1750 Hp
Technical UL (Output power, Heavy-Duty use)1250 Hp
Technical UL (Output power, Light-Overload use)1500 Hp
Frequency48 ... 63 Hz
Phases3-phase
IP ratingIP22
ProtocolCAN
Number of hardware interfacesIndustrial Ethernet 0
Altitude1000 m
Operating humidity (RHamβ)5 ... 95
Frame size3xR8i+3xR8i
SCIP944D8A5E-036D-404E-9036-0D3C1EA703AD Finland
IncludesControl unit
Sound78 dB(A)
Analog inputs4
Analog outputs4
Temperature ratingMaximum 40 °C
Ecodesign exemptionEnergy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c).
Multiple battery informationLithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g
Number of digital in (Outputs)14 / 10

Product details

The 3AXD50000145850: Normal-use output is 1400 kW at 1980 A; heavy-duty use is 1000 kW at 1481 A; light-overload use is 1300 kW at 1901 A. The UL equivalent ratings track the same current figures at 1750 Hp, 1250 Hp, and 1500 Hp respectively. For a procurement decision, the heavy-duty figure governs continuous motor load applications where the drive must hold torque through a stalled or high-inertia start — if the motor nameplate exceeds 1481 A at the rated voltage, this frame is undersized for that duty class.

Environmental and installation limits

Maximum ambient temperature is 40 °C, operating humidity 5–95 % RH, altitude 1000 m without derating. Enclosure is IP22 with NEMA Type 1 — suitable for indoor, non-condensing environments but not for washdown or dust-heavy areas. Sound pressure level is 78 dB(A); plan for panel attenuation if the drive is near operator stations.

Four analog inputs, four analog outputs, 14 digital inputs, 10 digital outputs. Communication is CAN; no onboard Industrial Ethernet. The control unit is included in the frame. Two lithium coin cells (BR2032, 3 V, 200 mAh) back up real-time clock and parameter storage — verify replacement interval per site maintenance schedule.

Regulatory and compliance notes

SCIP number 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland. WEEE category 4 (Large Equipment, any external dimension >50 cm). This regenerative drive is exempt from EU ecodesign energy-efficiency requirements under Regulation EU/2019/1781 §2.3.c.

Frequently asked questions

What are the key ratings of the 3AXD50000145850?

Normal-use output is 1400 kW at 1980 A; heavy-duty is 1000 kW at 1481 A; light-overload is 1300 kW at 1901 A. Input is 380–500 V three-phase, 48–63 Hz.

What is the SCIP number for this drive?

SCIP: 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland.

What is the maximum operating altitude?

1000 m without derating.

What enclosure and protection rating does it have?

NEMA Type 1, IP22.

MPN
3AXD50000145850