Skip to main content
ABB 3AXD50000145867 — AC Drives (VFD)

ABB 3AXD50000145867 ACS880-17 Drive, 1600 kW, 2270 A

MPN3AXD50000145867
Active

ABB ACS880-17 series, regenerative drive, order code 3AXD50000145867, 1600 kW normal use, 2270 A output, 380-500 V 3-phase.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000145867 — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency48 ... 63 Hz
Number of phases3-phase
3AXD50000145867 — Power & Current
ParameterValue
Output power, normal duty1600 kW
Output power, heavy duty1200 kW
Output power, light-overload duty1500 kW
Output current, heavy duty1698 A
Output current, normal duty2270 A
Output current, light-overload duty2179 A
3AXD50000145867 — Protection & Environmental
ParameterValue
Degree of protection (IP)IP22
NEMA enclosure typeType1
3AXD50000145867 — Mechanical
ParameterValue
Frame size3xR8i+3xR8i

Product details

The ABB 3AXD50000145867 is a regenerative drive rated for 1600 kW normal-use output at 2270 A, fed from a 380-500 V 3-phase supply. It is built in a 3xR8i+3xR8i frame with NEMA 1 enclosure and IP22 protection. The drive carries three distinct duty ratings: 1600 kW / 2270 A for normal use, 1500 kW / 2179 A for light-overload, and 1200 kW / 1698 A for heavy-duty. The heavy-duty figure governs continuous motor torque at high starting loads or demanding cycles; the light-overload rating covers applications with occasional peak demand above the normal curve.

Duty ratings and real-world fit

The light-overload figure (1500 kW) sits between them and matches applications like pumps or fans where occasional peak demand is the exception, not the rule.

Environmental limits and installation constraints

Rated for a maximum ambient of 40 °C, altitude up to 1000 m without derating, and operating humidity of 5-95% non-condensing. The 78 dB(A) sound level at full load means hearing protection is advisable in the drive room. The regenerative design is exempt from EU ecodesign efficiency reporting (Regulation EU/2019/1781, §2.3.c) — no energy-efficiency class to declare.

I/O and communication summary

The drive includes 14 digital I/O (10 outputs), 4 analog inputs, and 4 analog outputs. Communication is via CAN bus; no onboard Industrial Ethernet. The control unit is included. Two lithium coin cells (BR2032, 3 V, 200 mAh each) back up the real-time clock and parameter storage.

Frequently asked questions

What are the key electrical ratings?

Normal-use output is 1600 kW at 2270 A; heavy-duty is 1200 kW at 1698 A; light-overload is 1500 kW at 2179 A. Input is 380-500 V 3-phase, 48-63 Hz.

What enclosure and protection rating does it have?

NEMA Type 1 enclosure with IP22 degree of protection — indoor use, no washdown capability.

What is the SCIP number for this drive?

SCIP: 944D8A5E-036D-404E-9036-0D3C1EA703AD, registered in Finland.

MPN