Skip to main content
ABB 3AXD50000146086 — AC Drives (VFD)

ABB 3AXD50000146086 ACS880-37-0302A-5 Drive, 200 kW

MPN3AXD50000146086
Active

ABB ACS880-37, frame R11, 200 kW normal use (302 A), 380–500 V 3-phase, IP22, Type 1.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000146086 — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency48 ... 63 Hz
Number of phases3-phase
3AXD50000146086 — Power & Current
ParameterValue
Output power, normal duty200 kW
Output current, normal duty302 A
3AXD50000146086 — Protection & Environmental
ParameterValue
Degree of protection (IP)IP22
NEMA enclosure typeType1
3AXD50000146086 — Mechanical
ParameterValue
Frame sizeR11

Product details

Rating & Duty Selection

The ABB 3AXD50000146086 (ACS880-37-0302A-5) is an active drive rated 200 kW normal use and 302 A output current, suited for heavy industrial three-phase loads. For heavy-duty motor applications it carries 200 HP (260 A), and for light-overload use 250 HP (302 A) — the same 302 A limit as normal use but rated for higher short-term overload.

Environment & Mounting

Enclosure is IP22 / NEMA Type 1, intended for clean indoor installation. Frame R11 dimensions and a 77 dB(A) sound level factor into panel layout and noise limits. Altitude rating is 1000 m — operation above that requires derating per the product manual. Ambient humidity range is 5–95% non-condensing. Control board power backup uses two CR2032 lithium coin cells (3 V, 220 mAh each) for real-time clock and parameter retention during power-off.

Compliance & Lifecycle

SCIP declaration number 9ECED1FE-316A-4BF4-991E-2606BB5FE13A Finland is on file. This low-harmonic drive is exempt from EU ecodesign energy-efficiency requirements (Regulation 2019/1781, §2.3.d) — no IE class listed. UL-related ratings are present: heavy-duty 200 HP (260 A) and light-overload 250 HP (302 A). WEEE classification is Category 4 (Large Equipment).

Frequently asked questions

What is the SCIP number for this drive?

SCIP: 9ECED1FE-316A-4BF4-991E-2606BB5FE13A Finland.

What is the altitude rating?

Rated for installation up to 1000 m altitude. Above that, derating per the product manual is required.

What output power does it deliver in normal vs heavy-duty use?

Normal use: 200 kW, 302 A. Heavy-duty (UL): 200 HP, 260 A. Light-overload (UL): 250 HP, 302 A.

What input voltage and frequency does it accept?

380–500 V three-phase, 48–63 Hz.

MPN