Skip to main content
ABB 3AXD50000146109 — AC Drives (VFD)

3AXD50000146109 ABB ACS880-37-0414A-5 Drive, 250 kW, 414 A,

MPN3AXD50000146109
Active

ABB ACS880-37 series, 3AXD50000146109, 250 kW normal-use output, 414 A, R11 frame, IP22, 380-500 VAC 3-phase input.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000146109 — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency48 ... 63 Hz
Number of phases3-phase
3AXD50000146109 — Power & Current
ParameterValue
Output power, normal duty250 kW
Output power, heavy duty200 kW
Output power, light-overload duty250 kW
Output current, heavy duty361 A
Output current, normal duty414 A
Output current, light-overload duty393 A
3AXD50000146109 — Protection & Environmental
ParameterValue
Degree of protection (IP)IP22
NEMA enclosure typeType1
3AXD50000146109 — Mechanical
ParameterValue
Frame sizeR11

Product details

The 3AXD50000146109: The drive carries three duty curves. Normal use (Pn) delivers 250 kW at 414 A continuous — that's the number for a centrifugal pump or fan with a standard torque profile. Heavy-duty use (PhD) drops to 200 kW at 361 A, sized for constant-torque loads like a conveyor or extruder that need full torque across the speed range. Light-overload use (PlD) matches the normal-use power at 250 kW but current is 393 A, a middle ground for applications with moderate overload cycles. The UL heavy-duty rating is 300 Hp at 361 A and light-overload is 350 Hp at 414 A.

R11 frame — expect a cabinet footprint sized for a drive this class, with IP22 ingress protection (finger-safe, no dripping water). Maximum ambient is 40 °C, altitude derating starts above 1000 m. Operating humidity 5 to 95% non-condensing. Sound level is 77 dB(A) — not silent, but within range for a 250 kW drive in a machine room. The enclosure is NEMA Type 1 for indoor use.

I/O and control interface

Onboard I/O: 2 analog inputs, 2 analog outputs, 7 digital inputs, 5 digital outputs. Communication is CAN — no onboard Industrial Ethernet. The drive includes the control unit. For fieldbus connectivity beyond CAN, you'd add an optional adapter module. The battery pack (two CR2032 lithium coins) backs the real-time clock and parameter storage.

SCIP number 9ECED1FE-316A-4BF4-991E-2606BB5FE13A Finland is on file for EU waste and substance reporting. The drive is exempt from EU ecodesign efficiency requirements (Regulation EU/2019/1781, §2.3.d) because it's a low-harmonic type. WEEE category 4 — large equipment. No additional compliance documents (RoHS, REACH, UL) are listed in the spec record, but the UL duty ratings confirm UL listing for the heavy-duty and light-overload power levels.

Frequently asked questions

What are the key output ratings for this drive?

Normal-use output is 250 kW at 414 A. Heavy-duty use is 200 kW at 361 A. Light-overload use is 250 kW at 393 A. UL heavy-duty is 300 Hp at 361 A, and UL light-overload is 350 Hp at 414 A.

What is the input voltage and frequency range?

380 to 500 VAC three-phase, 48 to 63 Hz.

What enclosure and protection rating does it have?

IP22 ingress protection, NEMA Type 1 enclosure, frame size R11.

Does this drive have an Industrial Ethernet interface?

No. The onboard communication protocol is CAN. There are zero Industrial Ethernet hardware interfaces on this variant.

MPN