Skip to main content
ABB 3AXD50000146123 — AC Drives (VFD)

ABB 3AXD50000146123 ACS880-37 Drive, 355 kW, 503 A

MPN3AXD50000146123
Active

ABB ACS880-37 low-harmonic drive, 3AXD50000146123, 355 kW / 503 A normal use, 380-500 VAC 3-phase, Frame R11, IP22, CAN.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000146123 — Electrical
ParameterValue
Input voltage380 ... 500 V
Frequency48 ... 63 Hz
Number of phases3-phase
3AXD50000146123 — Power & Current
ParameterValue
Output power, normal duty355 kW
Output power, heavy duty315 kW
Output power, light-overload duty355 kW
Output current, heavy duty460 A
Output current, normal duty503 A
Output current, light-overload duty492 A
3AXD50000146123 — Protection & Environmental
ParameterValue
Degree of protection (IP)IP22
NEMA enclosure typeType1
3AXD50000146123 — Mechanical
ParameterValue
Frame sizeR11

Product details

Load Ratings and Duty Selection

The 3AXD50000146123: Three duty ratings are specified: normal-use (Pn 355 kW, In 503 A), heavy-duty (PhD 315 kW, IhD 460 A), and light-overload (PlD 355 kW, IlD 492 A). The heavy-duty figure governs continuous motor load for applications like conveyors or pumps where overload margin is needed; the normal-use rating suits variable-torque loads such as fans and centrifugal pumps. UL heavy-duty ratings are 400 Hp and 483 A.

Enclosure, Environment, and Compliance

The drive is housed in Frame R11 with an IP22 degree of protection and NEMA Type 1 enclosure, suitable for indoor installation in clean, dry environments. Maximum ambient temperature is 40 °C, altitude 1000 m, and operating humidity 5-95% non-condensing. Sound level is 77 dB(A). The low-harmonic design is exempt from EU ecodesign requirements (Regulation EU/2019/1781, §2.3.d). SCIP number is 9ECED1FE-316A-4BF4-991E-2606BB5FE13A Finland.

Built-in I/O includes 2 analog inputs, 2 analog outputs, 7 digital inputs, and 5 digital outputs. Communication is via CAN protocol; no onboard Industrial Ethernet port. A lithium coin cell (CR2032, 2 pcs) backs the real-time clock. The control unit is included in the delivery.

Frequently asked questions

What are the key power and current ratings?

Normal-use output is 355 kW and 503 A; heavy-duty is 315 kW and 460 A; light-overload is 355 kW and 492 A. UL heavy-duty rating is 400 Hp and 483 A.

What is the input voltage and frequency range?

Input voltage is 380-500 VAC three-phase, 48-63 Hz.

What enclosure and protection rating does it have?

Frame R11 with IP22 protection and NEMA Type 1 enclosure.

What communication protocols are supported?

CAN protocol is standard; no onboard Industrial Ethernet.

MPN