Skip to main content
ABB 3AXD50000200054 — AC Drive (VFD) 480V

ABB 3AXD50000200054 R11 Drive Control Unit, 355 kW

MPN3AXD50000200054
Active

ABB drive control unit, frame size R11, 355 kW normal use, 503 A output, IP20, 380-500 VAC 3-phase.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000200054 — Power & Output
ParameterValue
Output power, normal duty355 kW
Output current, normal duty503 A
Output power, heavy duty315 kW
Output current, heavy duty460 A
Output power, light overload355 kW
Output current, light overload492 A
Output current, light overload (UL rating)492 A
Apparent power output436 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)400 Hp
Standby power loss247 W
3AXD50000200054 — Input / Supply
ParameterValue
Input voltage range380 ... 500 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000200054 — Mechanical & Cooling
ParameterValue
Frame sizeR11
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000200054 — Environmental
ParameterValue
Temperature rating (max.)Maximum +55 °C
3AXD50000200054 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)400 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)483 A

Product details

What this unit is and what it drives

The ABB 3AXD50000200054 is a drive control unit in frame size R11, rated for 355 kW normal-use output (503 A) and 315 kW heavy-duty output (460 A) on a 380–500 VAC three-phase supply. The heavy-duty current rating of 460 A is the figure that governs continuous motor load in a constant-torque application — the normal-use 503 A assumes a lighter, variable-torque profile. Light-overload use (492 A) sits between the two, matching the normal-use power of 355 kW but at a slightly lower current.

Open-type enclosure with IP20 protection — suitable for a clean, dry cabinet, not for washdown or dust-laden areas. The unit is rated for operation up to +55 °C ambient and 4000 m altitude without derating; above that, expect to reduce current or forced-cool. Humidity range 5–95% RH non-condensing. Sound pressure at 75 dB(A) under load — noticeable in a small panel room, so factor in ear protection if the drive runs near operators.

Power quality and efficiency

Rated power factor of 1.0 and standby loss of 247 W. The IE2 efficiency level is standard for this class; note the ecodesign exemption — low-harmonic drives are not required to report energy-efficiency data under EU 2019/1781 §2.3.d, so the absence of an IE class on the nameplate is expected, not a defect. Apparent power output is 436 kV·A, which gives a rough sizing guide for the upstream transformer and cabling.

I/O and communications

Built-in analog I/O: 2 inputs, 2 outputs. Digital I/O: 6 inputs, 2 outputs. Communication is CAN-based — no onboard Industrial Ethernet (0 hardware interfaces listed). If the application requires PROFINET, EtherNet/IP, or Modbus TCP, an optional fieldbus adapter module must be added. The control unit includes a lithium coin cell (CR2032, 220 mAh) for real-time clock backup; two cells are fitted, total 6 g.

Frequently asked questions

What compliance documentation is available for this unit?

RoHS compliance per EU 2011/65/EU (date 20240508), REACH declaration (date 20250905, contains substances >0.1%), UL listing for heavy-duty and light-overload use, and SCIP number c44fe560-7ab6-4f91-9cdb-6ff4cf7e4d81 (Finland) for WEEE reporting.

What are the key electrical ratings for this drive control unit?

Normal-use output: 355 kW / 503 A. Heavy-duty output: 315 kW / 460 A. Light-overload output: 355 kW / 492 A. Input voltage: 380–500 VAC three-phase, 47.5–63 Hz. Apparent power: 436 kV·A.

MPN