Skip to main content
ABB 3AXD50000462902 — Inverter / VFD

ABB 3AXD50000462902 ACS580 Drive, 96 A, 75 HP, 480 V

MPN3AXD50000462902
Active

ABB ACS580 LV AC Packaged Drive, Frame Size R5, 3-phase, 380–500 V, 96 A / 75 HP Light-Overload, 77 A / 60 HP Heavy-Duty, IP21, NEMA Type 1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000462902 specifications
ParameterValue
Enclosure type NEMAType1
Input voltage380 ... 500 V
Technical UL (Output current, Heavy-Duty use)77 A
Technical UL (Output current, Light-Overload use)96 A
Technical UL (Output power, Heavy-Duty use)60 Hp
Technical UL (Output power, Light-Overload use)75 Hp
Frequency50/60 Hz
Phases3-phase
IP ratingIP21
Frame sizeR5

Product details

The ABB 3AXD50000462902 is an ACS580-series LV AC packaged drive with a built-in disconnect means, sized for 3-phase 380–500 V supplies. It delivers 96 A in light-overload duty (75 HP) and 77 A in heavy-duty use (60 HP) per UL listing. Frame size R5, IP21 enclosure, NEMA Type 1.

The heavy-duty current rating of 77 A at 480 V is the number that governs motor starting and overload — that's 60 HP continuous. The light-overload figure of 96 A (75 HP) applies where the load profile stays below 110% for most of the cycle. Both are UL-listed, so the drive lands in a panel without a separate branch-circuit protection argument. Input voltage range of 380–500 V covers common 400 V and 480 V industrial mains. The integrated disconnect means simplifies the incoming line section — one less component to source and wire.

IP21 and NEMA Type 1 means it's suited for clean indoor environments — no dripping water, no dust. The R5 frame size is a standard ABB footprint; mount it against a backplate with clearance for the top cable entry and the heatsink airflow. The disconnect handle protrudes, so factor that into the door cutout if panel-mounted.

Frequently asked questions

What are the key ratings for this drive?

It is a 3-phase 380–500 V drive, Frame Size R5, delivering 96 A light-overload (75 HP) and 77 A heavy-duty (60 HP) per UL. Enclosure is IP21 / NEMA Type 1 with integral disconnect.

What is the frame size of this drive?

Frame size R5.

What is the input voltage and frequency range?

Input voltage is 380–500 V, 3-phase, 50/60 Hz.

MPN
3AXD50000462902