Skip to main content
ABB 3AXD50001057633 — Inverter / VFD

ABB 3AXD50001057633 ACS880-37 VFD, 500 kW, 710 A

MPN3AXD50001057633
Active

ABB ACS880-37 VFD, 3AXD50001057633, 500 kW normal-use output, 710 A, 380-500 V 3-phase, IP22, frame R8i+R8i.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50001057633 key specifications
ParameterValue
Enclosure type NEMAType1
Input voltage380 ... 500 V
Output current, normal use710 A
Output current, Heavy-Duty use531 A
Output current, Light-Overload use682 A
Technical UL (Output current, Heavy-Duty use)531 A
Technical UL (Output current, Light-Overload use)682 A
Output power, normal use500 kW
Output power, Heavy-Duty use350 kW
Output power, Light-Overload use450 kW
Technical UL (Output power, Heavy-Duty use)450 Hp
Technical UL (Output power, Light-Overload use)500 Hp

All specifications

3AXD50001057633 additional specifications
ParameterValue
Frequency48 ... 63 Hz
Phases3-phase
IP ratingIP22
Altitude1000 m
Operating humidity (RHamβ)5 ... 95
Frame sizeR8i+R8i
Multiple battery informationLithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g

Product details

The ABB 3AXD50001057633 is rated for 500 kW normal-use output at 710 A, fed from a 380-500 V three-phase supply. Frame size R8i+R8i, IP22 enclosure, and a 48-63 Hz line input. This is a current-production unit.

Heavy-duty (PhD/IhD) drops to 350 kW / 531 A — that's the figure for high-start-torque or cyclic applications like crushers or extruders. Light-overload (PlD/IlD) sits at 450 kW / 682 A, suitable for variable-torque loads like fans and pumps where occasional overloads are brief. Under UL listing, the heavy-duty output is 450 Hp at 531 A, and light-overload is 500 Hp at 682 A. Pick the duty class that matches your motor's actual demand, not the headline number.

Physical and environmental notes

Frame R8i+R8i is a large cabinet-style form factor — plan for floor-mounting, not a panel. IP22 means protected against solid objects over 12 mm and dripping water; keep it indoors, away from washdown areas. Altitude rating is 1000 m without derating; above that, consult the manual for current reduction. Ambient humidity range 5-95% non-condensing. The drive includes two BR2032 lithium coin cells for the control board backup.

Frequently asked questions

What are the key output ratings for this drive?

Normal use: 500 kW / 710 A. Heavy-duty: 350 kW / 531 A. Light-overload: 450 kW / 682 A. UL heavy-duty: 450 Hp / 531 A. UL light-overload: 500 Hp / 682 A.

What frame size and enclosure does this drive have?

Frame R8i+R8i with IP22 protection. It is a large floor-mount cabinet drive.

What input voltage and frequency does it accept?

380-500 V three-phase, 48-63 Hz.

MPN