Skip to main content
ABB AF370-30-11-14 — Contactors

ABB AF370-30-11-14 Contactor, 3P, 361A, 250V Coil

MPNAF370-30-11-14

ABB AF370-30-11-14, 3-pole contactor, 361 A, 250 V coil, current lifecycle stage.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Product details

The ABB AF370-30-11-14 is a 3-pole contactor rated for 361 A, with a 250 V coil. It's a full-size power contactor for switching motor loads, resistive heaters, or other heavy AC loads in a control panel.

The 361 A rating is the conventional free-air thermal current (Ith) — the contactor's maximum continuous current in an open panel at 40 °C. For motor switching, derate to the AC-3 rating (typically around 300 A for this frame size), which governs the actual motor full-load current it can switch without accelerated contact wear. The 250 V coil is a control voltage — verify your control transformer or PLC output matches; common 230 V control circuits will pull this in, but a 24 VDC system won't.

This is a bolt-on contactor, not a DIN-rail snap-on — the AF370 frame uses screw terminals and a mounting plate. Plan for a 185 mm wide footprint and M8 bolting to the backplate. The 3-pole + 2 auxiliary contact configuration (30-11) gives one N.O. + one N.C. aux for status feedback or interlocking, which is standard for a reversing or star-delta starter.

Frequently asked questions

What are the key ratings of the AF370-30-11-14?

It is a 3-pole contactor rated for 361 A continuous current, with a 250 V coil. The description confirms the 3-pole, 361 A, 250 V coil configuration.

How do I source the AF370-30-11-14?

As a current-production part, it is sourced to order against an RFQ through the standard ABB distribution channel. No surplus or broker sourcing is necessary.

MPN
AF370-30-11-14