The ABB S281-K16A is a single-pole miniature circuit breaker from the S280 series, rated 16 A with a K-characteristic trip curve. It snaps onto standard DIN rail and is used for protecting branch circuits in distribution panels and control cabinets against overload and short circuit. The K-characteristic means the magnetic trip threshold is 8–12× In, making it suitable for loads with moderate inrush — motor starters, transformers, or lighting banks where a B- or C-curve might nuisance trip on startup. For a 16 A breaker, that translates to a magnetic trip between 128 A and 192 A.
Lifecycle and Sourcing
For volume or BOM-freeze purchases, this part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.