Skip to main content
ABB S803C-C16 — 3-Pole MCB (DIN Rail)

ABB S803C-C16 MCB, 3P, C-Curve, 16 A, 15 kA

MPNS803C-C16

ABB S800C series, S803C-C16 miniature circuit breaker, 3-pole, C-curve, 16 A, 15 kA interrupting capacity at 230 VAC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

S803C-C16 — Identification
ParameterValue
Number of poles3
S803C-C16 — Electrical
ParameterValue
Voltage (AC)230
Current (A)16
S803C-C16 — Protection
ParameterValue
Interrupting rating (AC)15 kA
S803C-C16 — Mechanical
ParameterValue
Mounting typeDIN Rail
S803C-C16 — Other specifications
ParameterValue
TypeTrip Curve C
Interrupt rating DC10 kA

Product details

What the ratings mean for a panel fit

The ABB S803C-C16 is a 3-pole miniature circuit breaker from the S800C series, rated 16 A with a C-curve trip characteristic. The 15 kA interrupting capacity at 230 VAC means it can safely clear a fault up to that level without welding its contacts or cascading failure upstream — critical for maintaining selectivity in a distribution board. On the DC side, it interrupts up to 10 kA, so it handles battery-backed control circuits or DC link protection in the same panel footprint.

Deployment context

Snaps onto standard DIN rail in any 3-phase panel — motor control centers, sub-distribution boards, or machine supply disconnects. The C-curve (5–10x In magnetic trip) suits moderate inrush loads like small motors, transformers, or lighting banks where a B-curve would nuisance-trip but a D-curve delays too long.

Frequently asked questions

Where can I buy the S803C-C16 and get a price?

The S803C-C16 is sourced through independent distribution channels. Submit an RFQ — availability and current pricing are confirmed at quote time.

What is the S803C-C16's amp rating and trip curve?

The S803C-C16 is rated 16 A with a C-curve trip characteristic (5–10x In magnetic trip).

Will the S803C-C16 drop into a panel specified for the S803S-D63?

Both mount on standard DIN rail, but the S803S-D63 is a 63 A D-curve breaker with 50 kA interrupting — different amp rating, trip curve, and fault capacity. The S803C-C16 is not a direct functional swap without recalculating the circuit protection.

MPN