Skip to main content
ABB 1SFA896110R7000

ABB 1SFA896110R7000 PSR37 Soft Starter, 208-600V AC

MPN 1SFA896110R7000
Active

ABB PSR37 soft starter, order code 1SFA896110R7000, with voltage ramp, 208–600 V AC operating range, 4xIe for 6s starting capacity, screw-terminal main connections.

$358.00 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

1SFA896110R7000 specifications
ParameterValue
Terminal typeScrew Terminal
Voltage208 ... 600 V AC
Frequency50/60 Hz
ProtocolFiledBusPlug(Optional)
Temp operating max60 °C
Temp operating min-25 °C

Product details

What it does on the line

The ABB PSR37 (1SFA896110R7000) is a soft start with voltage ramp rated for 208 … 600 V AC operation at 50/60 Hz, with a starting capacity of 4xIe for 6s — the figure that governs how heavy a load it can break away on a cold start. Ramp behaviour is dialed in on the front of the unit: ramp time 0 … 20 s, initial voltage during start 40 … 70 %, and a step-down special ramp of 100 … 60 % — a fixed profile, no current-limit function on board.

Control side and fieldbus

Control supply is 100 … 240 V AC; the control circuit runs at 24 V DC, so the panel PSU needs to carry both rails if the existing cabinet doesn't already. Communication is an optional FieldBusPlug — there is no inside-delta connection, so this is line-voltage starting only. Signal relays cover run and by-pass indication; fault signal relay and overload signal relay are not fitted, so those PLC inputs need to be sourced another way.

Overload, wiring and environment

There is no integrated electronic overload — ABB recommends pairing with an MS450 28 … 40 to cover the thermal trip envelope on this PSR37 frame, which means the overload sits as a separate BOM line directly below the starter. Main circuit accepts rigid 1 x 6 … 35 mm² on screw terminals; supply and control circuits take rigid 1 x 0.75 … 2.5 mm² on the same terminal style. Control-circuit tightening torque is 0.6 N·m (5.3 in·lb per the UL/CSA figure). Main terminals carry IP10 per IEC 60529 / IEC 60947-1 — finger-safe against incidental contact inside the panel, not a sealed enclosure.

Compliance documentation

RoHS compliance is documented per EU Directive 2011/65/EU and Amendment 2015/863 of 22 July 2019; the unit is classed as WEEE Category 5 small equipment, B2B supply channel.

MPN
1SFA896110R7000