Skip to main content
Schneider Electric A9C15180

Schneider Electric A9C15180 Acti9 CT Contactor, 25 A, 2P, 23

MPN A9C15180
Obsolete

Schneider Electric Acti9 CT contactor, A9C15180, 2P, 25 A AC-7A, 230 V AC 50 Hz coil, clip-on 35 mm DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9C15180 key specifications
ParameterValue
Control typeRemote control
Control signal typeMaintained
Main product or component typeContactor
Voltage250 V AC 50 Hz
Coil voltage230 V AC 50 Hz
Insulation voltage ui500 V AC
Current25 A AC-7 A 8.5 A AC-7B
Frequency100 switching operations/day
Poles2P
Utilization categoryAC-1 conforming to IEC 60947-4
Temp storage max60 °C
Temp storage min-40 °C

All specifications

A9C15180 additional specifications
ParameterValue
Temp operating max60 °C
Temp operating min-5 °C
Storage temperature-40...60 °C
Pollution degree2
ColorWhite
Depth66 mm
Width18 mm
Height90 mm
ApplicationControl circuit
Operating temperature-5...60 °C

Product details

It clips onto a 35 mm symmetrical DIN rail and is rated for 25 A in AC-7A utilisation category (resistive/lighting loads) and 8.5 A in AC-7B (motor loads for household appliances), per IEC 60947-4. The coil is 230 V AC at 50 Hz, drawing 15 VA inrush and 3.8 VA hold-in power.

The 8.5 A AC-7B rating covers small motor loads like fans or pumps in appliances. The 230 V AC coil means it's a line-voltage control device; plan for a separate control transformer if your panel runs 24 VDC logic. The 2 NO pole configuration gives you two independently switched power paths, each rated at the same operational current. Mounting is clip-on to standard 35 mm DIN rail. IP20 body protection means it's safe from finger contact but not washdown; install inside an enclosure rated at least IP40. The tunnel-type terminals accept up to 6 mm² rigid or 2.5 mm² flexible per pole, with a tightening torque of 0.8 N.m. Strip length is 10 mm.

The contactor is designed to IEC 61095 and EN 61095, the standard for electromechanical contactors for household and similar purposes. It carries a pollution degree 2 rating and is tropicalised to 2 levels per EN 61095 and IEC 1095, meaning it withstands damp heat conditions. Operating altitude is rated to 2000 m, and relative humidity tolerance is 95% at 55 °C. The noise level is listed at 30 dB — essentially silent operation in a panel environment.

MPN
A9C15180