Skip to main content
Schneider Electric A9C63425

Schneider A9C63425 Reflex iC60N Ti24 25A 4P Curve D MCB

MPN A9C63425
Active

Schneider Electric Reflex iC60N Ti24, A9C63425, integrated control circuit breaker, 25 A, 4 poles, curve D, 20 kA Icu at 230 V AC.

$389.64 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9C63425 specifications
ParameterValue
Trip unit typeThermal-magnetic
Main product or component typeIntegrated control circuit breaker
Coil voltage230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC
Insulation voltage ui500 V AC
Breaking capacity20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
IP ratingIP20
Pollution degree3
ColorWhite
Depth77 mm
Width117 mm
Height84 mm
Electrical life cyclesAC-1: 50000 cycles AC 50 Hz
Mechanical life cycles50000 cycles
ApplicationDistribution Control

Product details

The Schneider Electric A9C63425 is a Reflex iC60N Ti24 integrated control circuit breaker from the Acti9 range, combining overcurrent protection with remote switching in a single 4-pole package. The part is certified to EN/IEC 60947-2 and carries a 20 kA Icu breaking capacity at 230 V AC, dropping to 10 kA at 380–415 V AC. That SCCR headroom is enough for most distribution sub-panels in industrial control cabinets; the 500 V AC rated insulation voltage (Ui) confirms it lives on 400 V three-phase networks without derating.

Control and signalling — what the Ti24 suffix means

Ti24 denotes the control interface: the breaker accepts a maintained or pulsed low-voltage signal (24 V AC/DC, 48 V AC/DC, or 230 V AC) on its integrated control coil, so a PLC or remote pushbutton can toggle the main contacts without a separate contactor. Local status is visible through the green ON LED, red fault LED, and flashing indicators for tripped, overheat, and ready states. The control circuit voltage options (24 V AC/DC, 48 V AC/DC, 230 V AC) let you match the panel's existing control voltage — no extra transformer for the coil.

The fixed mounting mode and 13 × 9 mm pitch footprint (117 mm wide, 84 mm high, 77 mm deep) occupy four modular spaces in the enclosure. Tropicalisation class 2 means it withstands 93 % RH at 40 °C, so coastal or unconditioned plant rooms are fine. The padlockable OFF position (provision for padlocking) satisfies lockout/tagout requirements without an accessory.

MPN
A9C63425