Skip to main content
Schneider Electric A9C66216

Schneider Electric A9C66216 Reflex iC60H Ti24 16A 2P curve D

MPN A9C66216
Obsolete

Schneider Electric Acti9 Reflex iC60H Ti24, integrated control MCB, 16 A, 2P, curve D, 30 kA breaking capacity.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9C66216 specifications
ParameterValue
Trip unit typeThermal-magnetic
Main product or component typeIntegrated control circuit breaker
Coil voltage230 V AC 50/60 Hz 24 V AC 50/60 Hz 48 V AC 50/60 Hz 24 V DC 48 V DC
Insulation voltage ui500 V AC
Breaking capacity30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
IP ratingIP20
Pollution degree3
ColorWhite
Depth77 mm
Width81 mm
Height84 mm
Electrical life cyclesAC-1: 50000 cycles AC 50 Hz
Mechanical life cycles50000 cycles
ApplicationControl Distribution

Product details

The Schneider Electric A9C66216 is a Reflex iC60H Ti24 integrated control circuit breaker — a thermal-magnetic MCB with a built-in remote control module, rated 16 A, 2 poles, curve D, from the Acti9 range. The 30 kA breaking capacity at 230 V AC (15 kA at 415 V) per EN/IEC 60947-2 means it can safely interrupt high fault currents without upstream cascading — a key spec for panel SCCR compliance.

Control and integration

The Ti24 control module accepts multiple signal types: maintained very low voltage, impulse, or maintained 230 V AC, 24 V AC/DC, or 48 V AC/DC — so the same part works with a remote pushbutton, PLC digital output, or building management contact. Local signalling via a flashing/green/red LED indicates device ready, tripped, overheat, or ON — useful for quick fault isolation without a meter.

Environmental and durability

Electrical durability of 50,000 cycles in AC-1 (resistive load) and matching mechanical durability — aligns with typical panel life for a controlled distribution circuit. IP20 finger-safe terminals per IEC 60529; earth-leakage protection requires a separate Vigi block (not integrated).

MPN
A9C66216