Skip to main content
Schneider Electric A9F03416

A9F03416 Acti9 iC60N MCB, 16 A, 4P, B-Curve, 36 kA

MPN A9F03416
Active

Schneider Electric Acti9 iC60N, A9F03416, miniature circuit breaker, 16 A, 4 poles, B-curve, 36 kA Icu at 12-133 V AC, thermal-magnetic trip, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F03416 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C

All specifications

A9F03416 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width72 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The Schneider Electric A9F03416 is an Acti9 iC60N miniature circuit breaker rated 16 A with four protected poles and a B-curve magnetic trip threshold of 4 x In ±20 %.

The 4-pole body (91 mm high, 78.5 mm deep) fits most distribution boards without crowding the cover. Strip length is 14 mm. IP20 finger-safe terminals are standard for enclosed panel use; no washdown rating here, so keep it behind the panel door.

The Acti9 iC60N family is a broad, widely stocked line; the A9F03416 is a standard catalogue variant (16 A, 4P, B-curve).

MPN
A9F03416