Schneider Electric Acti9 iC60H miniature circuit breaker, 25 A, 2 poles, D curve, 42 kA breaking capacity at 133 V AC, thermal-magnetic trip, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F08225 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C

All specifications

A9F08225 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width36 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The Schneider Electric A9F08225 is an Acti9 iC60H miniature circuit breaker rated 25 A with a D tripping curve, 2 protected poles, and a 42 kA Icu breaking capacity at 12...133 V AC. It's a thermal-magnetic MCB meant for distribution panels where you need high short-circuit interruption and selective coordination downstream. The D curve (magnetic trip at 12 x In ±20%) handles motor and transformer inrush without nuisance tripping — that's the main reason you'd pick this over a C curve in the same iC60 family.

At 220...240 V AC that drops to 30 kA Icu, and at 380...415 V AC it's 15 kA Icu. The D curve trips magnetically at 12 x In ±20%, so for a 25 A breaker that's between 240 A and 360 A instantaneous. That delay lets motor starting currents (typically 6-8 x FLA) pass through without tripping, but still catches hard shorts. The thermal element handles overloads: it'll hold 25 A continuous and trip on a sustained 32 A load after a few minutes, depending on ambient. Overvoltage category IV means it's suitable for the main distribution board at the service entrance, not just sub-panels.

That's enough for a 25 A feed — typically 4 mm² or 6 mm² copper for the load side. The toggle switch has a trip indicator that pops a red flag when it's tripped, so you can spot a faulted circuit at a glance in a crowded panel.

MPN