Skip to main content
Schneider Electric A9K23150

Schneider Electric A9K23150 Acti9 iK60 MCB, 50 A, 1P, B Curv

MPN A9K23150
Obsolete

Schneider Electric Acti9 iK60N miniature circuit breaker, A9K23150, 1P, 50 A, B-curve, 6 kA Icn at 230 V AC, thermal-magnetic trip, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9K23150 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage230 V AC 50/60 Hz
Insulation voltage ui440 V AC 50/60 Hz conforming to EN/IEC 60898-1
Breaking capacity6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
IP ratingIP20
Terminal pitch18 mm between devices
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C

All specifications

A9K23150 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree2 conforming to EN/IEC 60898-1
ColorWhite
Depth78.5 mm
Width18 mm
Height85 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

The Schneider Electric A9K23150 is a 1-pole miniature circuit breaker from the Acti9 iK60N series, rated 50 A at 30 °C with a B-curve trip characteristic (magnetic release between 3 and 5 times In). Breaking capacity is 6000 A Icn at 230 V AC, 50/60 Hz, conforming to EN/IEC 60898-1 — sufficient for most domestic and light commercial panelboards where the prospective short-circuit current stays under that threshold.

In a warmer panel (40 °C or above), derate per the manufacturer's thermal curve — the 50 A figure is the starting point, not a hard limit across all environments. B-curve means the magnetic trip operates at 3 to 5 times rated current (150 A to 250 A for this 50 A unit). That makes it a good fit for resistive and general-purpose loads with modest inrush — lighting circuits, socket outlets, small heaters. Not ideal for motor circuits or transformers where higher inrush would nuisance-trip a B-curve; those call for a C or D curve.

Width is 18 mm (2 x 9 mm pitches), so it occupies a single module slot in a distribution board. Connection pitch between devices is 18 mm — standard for modular MCBs. IP20 finger-safe protection on the front face — suitable for enclosed panels only.

MPN
A9K23150