Skip to main content
Schneider Electric A9KF71225BQ

Schneider Electric A9KF71225BQ Acti9 K60 MCB, C-Curve 25A 2P

MPN A9KF71225BQ
Active

Schneider Electric Acti9 K60, miniature circuit-breaker, 2P, 25 A, C curve, 10 kA Icn at 415 V AC 50/60 Hz, DIN rail mount, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9KF71225BQ key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity10000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
IP ratingIP20
Temp storage max85 °C
Temp storage min-25 °C
Temp operating max55 °C
Temp operating min-5 °C
Storage temperature-25...85 °C
Pollution degree2

All specifications

A9KF71225BQ additional specifications
ParameterValue
ColorWhite
Depth70 mm
Width36 mm
Height81 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-5...55 °C

Product details

The Schneider Electric A9KF71225BQ is a 2-pole miniature circuit-breaker from the Acti9 K60 series, rated 25 A with a C-curve trip characteristic. It's a thermal-magnetic MCB built to EN/IEC 60898-1, meaning it's sized for final-circuit protection in distribution boards — lighting, socket outlets, small motor loads, that kind of duty.

The limitation class is 3 per EN/IEC 60898-1, which means it lets through less fault energy than a class 1 or 2 device — helps with downstream coordination and reduces arc-flash stress on the wiring. Rated 25 A continuous, 2 protected poles, so it switches both line conductors in a single-phase or split-phase circuit. The 2 N.m tightening torque on the tunnel terminals (accepts 1 to 25 mm² rigid, 1 to 16 mm² flexible) is standard for this class — don't overtighten; the terminal can deform. Strip length is 14 mm, which is what the tunnel needs for full conductor grip. Not rated for outdoor or wet-environment installation without an enclosure; IP20 means finger-safe terminals but no water ingress protection.

The 36 mm width (4 x 9 mm pitches) is the standard 2-module footprint for a 2P MCB — plan your rail fill accordingly. Height is 81 mm, depth 70 mm; it'll fit most domestic and industrial enclosures without clearance issues. The toggle actuator is manual, no auxiliary contact or shunt trip built in (no local signalling). If you need remote status or tripping, you'll add the appropriate Acti9 accessory alongside it.

MPN
A9KF71225BQ