Schneider Electric A9N18524

Schneider Electric A9N18524 Acti9 C120H MCB, 100 A D Curve 4

MPN A9N18524
Obsolete

Schneider Electric Acti9 C120H miniature circuit breaker, A9N18524, 4-pole, 100 A, D curve, 15 kA breaking capacity at 400 V AC, clip-on 35 mm DIN rail.

$142.46 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9N18524 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz 230...400 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max70 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-30 °C
Storage temperature-40...70 °C
Pollution degree3 conforming to IEC 60947-2

All specifications

A9N18524 additional specifications
ParameterValue
ColorWhite
Depth73 mm
Width108 mm
Height81 mm
Electrical life cycles5000 cycles conforming to IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...60 °C

Product details

The A9N18524 is a 4-pole Acti9 C120H miniature circuit breaker rated 100 A at 30 °C, with a D trip curve (magnetic trip between 10 and 14 times In). The 15 kA Icn at 400 V AC (per EN/IEC 60898-1) tells you it can clear a fault up to that level without welding its contacts; the IEC 60947-2 ratings go higher (30 kA Icu at 240 V) for industrial panel coordination.

D curve vs motor loads — the real selector

The D curve's 10–14 x In magnetic trip window is the deciding spec for motor circuits. A 100 A B-curve breaker trips magnetically at 3–5 x In — 300–500 A — which a 30 kW motor's starting surge can exceed. The D-curve on this C120H holds through 1000–1400 A peak, so it clears only a hard short, not a healthy start. That's the difference between a breaker that stays in and one that drops a conveyor on every restart.

Active production — no lifecycle worry

Current production, no phase-out or NRND notice on this order code. The Acti9 C120H series is Schneider's standard high-current MCB line for distribution boards and sub-distribution panels.

Dual-standard certification — what it covers

Certified to both EN/IEC 60898-1 (the MCB standard for household and similar installations) and EN/IEC 60947-2 (the industrial circuit-breaker standard). The 60898-1 rating gives you the Icn of 15 kA at 400 V for general distribution; the 60947-2 ratings give you Icu values at higher fault levels — 30 kA at 240 V, 15 kA at 415 V — for industrial panels where the prospective short-circuit current is known.

MPN
A9N18524