Skip to main content
Schneider Electric A9N19679

Schneider Electric A9N19679 DPN Vigi RCBO, 40 A, 30 mA, Type

MPN A9N19679
Obsolete

Schneider Electric Acti9 DPN Vigi, Type AC earth-leakage circuit breaker, 1P+N, 40 A, B curve, 300 mA sensitivity, 6 kA Icn at 230 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9N19679 specifications
ParameterValue
Control typeToggle
Product typeType AC
Trip unit typeThermal-magnetic
Main product or component typeEarth leakage circuit breaker
Voltage230 V AC 50/60 Hz
Insulation voltage ui400 V AC conforming to EN 61009
Breaking capacity6000 A Icn at 230 V AC 50/60 Hz conforming to EN 61009
Temp storage max60 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C
Storage temperature-40...60 °C
Pollution degree3 conforming to EN 61009
ColorWhite
Electrical life cycles10000 cycles conforming to IEC 61009
Mechanical life cycles20000 cycles
Operating temperature-5...60 °C

Product details

It combines a 40 A thermal-magnetic MCB (B curve, tripping between 3 and 5 times In) with integrated 300 mA Type AC earth-leakage detection in a single 1P+N module. Rated breaking capacity is 6 kA Icn at 230 V AC, 50/60 Hz, per EN/IEC 61009. That covers the majority of residential and light commercial final circuits in most European installations. The 300 mA sensitivity is a common earth-leakage threshold for protection against fire risk rather than direct personal shock — 30 mA units are used for personnel protection.

Occupies 4 modules of 9 mm pitch — 36 mm total width. Neutral is on the left, phase on the right. The toggle switch provides local ON/OFF indication and manual control.

Designed and certified to EN/IEC 61009-1 and EN/IEC 61009-2-1. Pollution degree 3, overvoltage category III, tropicalisation class 2, limitation class 3 — all per EN 61009. Rated insulation voltage 400 V AC. Operating altitude up to 2000 m, ambient storage range -40 to +60 °C, relative humidity 95 % at 55 °C. Electrical durability 10,000 cycles, mechanical durability 20,000 cycles.

MPN